Sentric np fuse switch disconnectors, General data – Siemens AC-21A User Manual

Page 18

background image

Siemens LV 10 · 2004

7/18

SENTRIC NP Fuse Switch Disconnectors

General data

7

Technical specifications

1) 125/160 A only with 3NY1 236 supply terminals and with 21 mm wide fuse

links 3NY1 822 (125 A) and 3NY1 824 (160 A); see Accessories.

2) Only for isolating links; otherwise note instructions of the fuse manufac-

turer.

3) For no-load switching (AC-20 B, DC-20 B), DC voltages up to DC 690 V

can be applied.

4) For safety monitoring max. 690 V.

5) For pollution severity 2, the switch disconnectors can be used up to 1000 V

AC-20 B, DC-20 B (no-load switching).

6) Conducting paths in series: 3 at 3NP40; 2 at 3NP42, 3NP43 and 3NP44.

Standards

IEC 60947-1, IEC 60947-3, VDE 0660 Part 107

Type

3NP40 1

3NP40 7

3NP42 7

3NP43 7

3NP44 7

Rated uninterrupted current I

u

A

160

1)

160

250

400

630

For fuse links acc. to DIN 43620

Size

00C/000

00

1 and 0

2 and 1

3 and 2

Continuous thermal current I

th

A

160

1)

160

250

400

630

Rated operating voltage

U

e

AC 50 Hz/60 Hz

V

690

690

DC

V

220
(3 conducting paths in series)

440
(2 conducting paths in series)

Rated insulation voltage

U

i

V

690

690

800

4)

800

4)

800

4)

Rated impulse withstand voltage

U

imp

kV

6

6

6

6

6

Rated conditional short-circuit current with fuses
(on rapid closing)

With fuse links
Rated current

Size/A

000/100 (35)

00/160

1/250

2/400

3/630

at AC 400 V (690 V)

kA (rms value)

50 (50)

50

50

50

50

Maximum permissible let-through I

2

t value

kA

2

s

56 (7.8)

158

551

1515

4340

Permissible let-through current of the fuse

kA (peak value)

11 (5)

15

25

35

55

Short-circuit strength with fuses
(with closed disconnector)

With fuse links
Rated current

Size/A

000/100

00/160

1/250

2/400

3/630

at 690 V

kA (rms value)

100

50

50

50

50

Permissible let-through current of the fuse

kA (peak value)

15

15

25

35

55

Rated making and breaking capacity
(Feed-in from top or bottom)

At AC 400 V, with fuse links
or isolating links

Size

000

00

1

2

3

Rated breaking current I

c

(p.f. = 0.35)

A (rms value)

800 (p.f. = 0.45)

800

2000

3200

5040

Rated operating current I

e

at

AC-21B, AC-22B
AC-23B

A
A

160
100

160
100

250
250

400
400

630
630

At AC 500 V, with fuse links
or isolating links

Size

000

00

1

2

3

Rated breaking current I

c

(p.f. = 0.35)

A (rms value)

320 (p.f. = 0.45)

320

750

1200

1890

Rated operating current I

e

at

AC-21 B
AC-22B
AC-23B

A
A
A

160
100
40

160
100
40

250
250

400
400

630
630

At AC 690 V, with fuse links
or isolating links

Size

000

00

1

2

3

Rated breaking current I

c

(p.f. = 0.35)

A (rms value)

200/240
(p.f. = 0.45/0.95)

200/240
(p.f. = 0.45/0.95)

375

600

945

Rated operating current I

e

at

AC-21 B
AC-22B
AC-23B

A
A
A

160
50
25

160
50
25

250

400

630

At DC 220 V/240 V, with fuse links

3)5)6)

or isolating links

Size

000

00

1

2

3

Rated operating current I

e

at

220 V DC-23B/DC-21B
440 V DC-21B

A
A

80/160

80/160


250


400


630