SENTRIC NP Fuse Switch Disconnectors
General data
7
1) Only for isolating links; otherwise note instructions of the fuse manufac-
turer.
Standards
IEC 60 947-1, IEC 60 947-3, VDE 0660 Part 107
Type
3NP40 1
3NP40 7
3NP42 7
3NP43 7
3NP44 7
Capacitor switching capacity
at AC 400 V
Capacitor power
kvar
50
50
–
–
–
Rated current I
n
A
72
72
–
–
–
at AC 525 V
Capacitor power
kvar
50
50
–
–
–
Rated current I
n
A
55
55
–
–
–
Permissible ambient temperature
°C
–25 ... +55
1)
for operation, –50 ... +80 for storage
Mechanical endurance
Operations
2000
2000
1600
1000
1000
Degree of protection
(with respect to the operator side)
Without molded-plastic masking frame/cable
lug cover
IP00 (3NP40 with box terminal and properly connected conductors: IP20)
With molded-plastic blanking plate/cable lug
cover
IP30 (contacts closed), IP20 (contacts open)
Power loss of the switch disconnector at I
th
(plus power loss of the fuse links)
a
Without busbar adapter
W
4.5 (at 100 A)
10
15
30
47
With busbar adapter
W
8.5 (at 100 A)
20
47
83
127
Main conductor connection
Flat pad connection for cable lug,
max. conductor cross-section (stranded)
mm
2
–
up to 2 × 70
(M 8)
up to 150
(M 10)
up to 240
(M 10)
up to 2 × 240
(M 12)
Box terminal/supply terminal
(finely stranded with end sleeve)
mm
2
1.5 ... 50 (35)
2.5 ... 70 (50)
70 ... 150
120 ... 240
150 ... 300
Conductor bar (width x thickness)
mm
–
22 Ч 5
22–30 Ч 5–10
22–30 Ч 5–10
25–40 Ч 5–10
Louvered Cu strips, unperforated in terminals
(width × thickness)
mm
8 × 8
up to 9 × 8
up to 16 × 8
up to 20 × 10
up to 24 × 10
Tightening torque for terminal screws
For flat pad connection
Nm
–
10 ... 12
25
25
30
With SIGUT box terminal/connection terminal
Nm
3 ... 3.5
8 ... 10
6
8
8
Auxiliary switch 1 CO (Accessory)
3NY3 035 AC 50 Hz/60 Hz up to 230 V
Rated operating current I
e
at AC-14
A
0.25 (I
th
= 5 A), at DC 24 V: I
e
= 0.45 A; flat connector to DIN 46244: A 2.8 × 0.5
3NY3 030 AC 50 Hz/60 Hz up to 230 V
Rated operating current I
e
at AC-13
A
0.1 (I
th
= 0.1 A); plug-in sleeve to DIN 46245: A 2.8 – 1
Permissible mounting position
Vertical or horizontal (no reduction in specified switching capacity)