Siemens LV 10 · 2004

7/2

Switch Disconnectors and Fuses

Introduction

7

Overview

Type

3LD20

3LD21

3LD22

3LD25

3LD27

3LD28

SENTRIC LD main control and EMERGENCY-STOP switches from 16 A to 125 A

Rated uninterrupted current

I

U

at 35 °C ambient temperature

A

16

25

32

63

100

125

Rated operating voltage

U

e

V

690

690

690

690

690

690

AC-3 motor load switch
operational switching of individual motors
at 220 ... 240 V

kW

3.0

4.0

5.5

11.0

18.5

22.0

at 380 ... 440 V

kW

5.5

7.5

9.5

18.5

30.0

37.0

at 660/690 V

kW

5.5

7.5

9.5

15.0

22.0

30.0

AC-23A main control switch,
maintenance switch
Frequent, but not operational switching of
individual motors
at 220 ... 240 V

kW

4.0

5.0

6.0

11.0

18.5

22.0

at 380 ... 440 V

kW

7.5

9.5

11.5

22.0

37.0

45.0

at 660/690 V

kW

7.5

9.5

11.5

18.5

30.0

37.0

Switch versions

Front mounting
• Central

• Four-hole

Base mounting
• Central

• Four-hole

Distribution board mounting

Molded-plastic enclosure
• Heavy-gauge threaded joints

• Metric screws

Switch accessories

4th pole (N conductor)
(leading switch-on,
delayed switch-off contact)

N terminal

PE/ground terminal

Auxiliary contacts
1 NO + 1 NC

1 NO

1 NC