Figure 32 figure 30, Figure 29 figure 31 – Superior DT-400CMP User Manual

Page 15

background image

15

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

*Firestop/Spacer (SV4.5HF) shown

on the exterior side of the wall. It

may also be installed on the

interior side.

SV4.5 HTSS

Termination

Shown.

10

¹⁄₂"

(267 mm)

7"

(178)

5

¹⁄₈"

(130 mm)

12

¹⁄₈"

(308 mm)

Note: Centerline of Vent

Piping is NOT the Same as

the Centerline of the

Framed Opening.

6 to 48 inch Vent Section,

Telescopic vent section,

Elbow or Appliance Collar

See Figure 9 on page

7 for Min. Distance to

Base of Appliance.

Base of Appliance

3"

(76 mm)

1"

(25.4 mm)

*Note - Firestop/Spacer integral

with round termination

(SV4.5HTR)

See Venting Figures for Use

Restrictions on the Horizontal

Round Termination (SV4.5HTR).

Adapter

SV4.5RCH

*Note - When using Secure Flex

use Firestop/Spacer SF4.5HF

*Firestop/Spacer (SV4.5HF) shown

on the exterior side of the wall. It

may also be installed on the

interior side.

SV4.5 HTSSL

Termination

10

¹⁄₂"

(267 mm)

7"

(178)

5

¹⁄₈"

(130 mm)

12

¹⁄₈"

(308 mm)

Note: Centerline of Vent Piping is

NOT the Same as the Centerline of

the Framed Opening.

6 to 48 inch Vent Section,

Elbow or Appliance Collar

See Figure 9 on page 7

for Min. Distance to

Base of Appliance.

Base of Appliance

3"

(76 mm)

1"

(25.4 mm)

*When using Secure Flex, use

Firestop/Spacer (SF4.5HF)

1

¹⁄₄" Maximum Recess of Square

Termination into Exterior Finishing
Material. Round Termination may
not be recessed at all.

Exterior Surface of Framing

6 in. to 10

¹⁄₄ in.

(152 mm to 260 mm)

Exterior Surface of Siding

Minimum wall thickness

*6 in. (152 mm)

Interior Surface of Finished Wall

Maximum wall thickness

10

¹⁄₄ in. (260 mm)

Maximum Extent of

Vent Run Sections

Relative to Exterior

Surface of Framing

Last Vent Section. Use
Telescopic Vent Section
(SV4.5LA), If Necessary

Adapter

SV4.5RCH

SV4.5HTSS Short

Square Termination

Shown

*Note - Firestop/Spacer

(SV4.5HF) required, but

not shown for clarity.

*Cut termination collar

for wall thicknesses

less than 6 in. (152 mm).

Siding

Stucco

SV4.5HTSS Short Square

Termination Shown

*When using Secure Flex, use

Firestop/Spacer SF4.5HF

Siding

Stucco

1

¹⁄₄" Maximum Recess of

Square Termination into
Exterior Finishing Material

Exterior Surface of Framing

Exterior Surface of Siding

Minimum wall thickness

*10

³⁄₄ in. (273 mm)

Interior Surface of

Finished Wall

Maximum wall thickness

20 in. (508 mm)

Maximum Extent of

Vent Run Sections

Relative to Exterior

Surface of Framing

Last Vent Section

SV4.5HTSSL Long
Square Termination

*When using Secure Flex, use

Firestop/Spacer SF4.5HF.

Termination Securing

Screw

SV4.5HTSSL Long
Square Termination

*Cut termination collar

for wall thicknesses

less than 10

³⁄₄ in. (273 mm).

10

³⁄₄ to 20 in.

(273 to 508 mm)

*Note - Firestop/Spacer

(SV4.5HF) required, but not

shown for clarity.

Figure 32

Figure 30

Installing Long Square HorizontalTermination (SV4.5HTSSL)

Figure 29

Figure 31

If the terminus of the last section is not within
this distance, use the telescopic vent section
SV4.5LA,
as the last vent section. For wall
thicknesses greater than that shown in

Figure

31, refer to table 3 on page 16. This table lists
the additional venting components needed (in
addition to the termination and adapter) for a
particular range of wall thicknesses.

Installing Square HorizontalTermination (SV4.5HTS) Short Square Horizontal

Termination (SV4.5HTSS) Round Horizontal Termination (SV4.5HTR)

Connecting/Recessing

Square (SV4.5HTS)

Short Square (SV4.5HTSS)

or Round (SV4.5HTR)

Horizontal Termination

Connecting/Recessing

Long Square Horizontal

Termination (SV4.5HTSSL)

L. Install Firestop/Spacer at exterior wall -
When using either of the square terminations,
install SV4.5HF (Secure Vent), or SF4.5HF
(Secure Flex) firestop/spacer over the opening
at the exterior side of the framing, long side up,
with the 3 inch spacer clearance at the top as
shown in

Figure 29 or 30, and nail into place.

(The Firestop/Spacer may be installed over the
opening at the interior side of the framing.)
When using the round termination, a separate
firestop/spacer is not required since this termi-
nation has integral spacers which provide the
same function as a separate firestop/spacer.

K. When using square (SV4.5HTS) or short
square (SV4.5 HTSS) horizontal termination
- attach termination adapter -
Attach the adapter (adapter - SV4.5RCH - pro-
vided with the termination) to the vent section or
telescoping vent section), elbow or appliance
collar as shown in

Figure 29 in the same manner

as any SV4.5 vent component (refer to Step E).

When using long square (SV4.5HTSSL)
horizontal termination
-
Assemble the vent system to point where the
terminus of the last section is within 0 in. (0
mm) to 9

³⁄₄ in. (248 mm) inboard of the

exterior surface to which the termination is to
be attached, see

Figure 32.