Siemens RS-485 User Manual
Page 9
9/14
Siemens Building Technologies
CC1A7865.1en
HVAC Products
31.10.2002
Address tables
Address
Data
type
Access
Parameter
Value range
Default
value
0x0000
float
R / O
Actual value E1
0x0002
float
R / O
Actual value E2
0x0004
float
R / O
Actual value E3
0x0006
float
R / W
Current setpoint
0x0008
float
R / W
SP1
First setpoint
SPL...SPH
0
0x000A
float
R / W
SP2 (=dSP)
Second setpoint
SPL...SPH
0
Address
Data
type
Access
Parameter
Value range
Default
value
0x000C
float
R / W
AL
Limit value limit comparator
-1999...9999
0
0x000E
float
R / W
Pb1
Proportional band
0.1...9999
10
0x0010
float
R / W
dt
Derivative action time
0...9999
80
0x0012
float
R / W
rt
Integral action time
0...9999
350
0x0014
float
R / W
db
Dead band (neutral zone)
0.0...100.0
1
0x0016
float
R / W
tt
Actuator running time
10...3000
15
0x0018
float
R / W
Hys1
Switch-on threshold
0...-199.9
-5
0x001A
float
R / W
Hys2
Switch-off threshold, bottom
0...Hys3
3
0x001C
float
R / W
Hys3
Switch-off threshold, top
0.0...999.9
5
0x001E
float
R / W
q
Reaction threshold
0.0...999.9
0
0x0020
float
R / W
H
Heating curve slope
0.0...4.0
1.0
0x0022
float
R / W
P
Parallel displacement
room temperature
-90...90
0
Address
Data
type
Access
Parameter
Value range
Default
value
0x0024
char [4]
R / W
C111
9030
0x0026
char [4]
R / W
C112
0010
0x0028
char [4]
R / W
C113
0110
0x002A
char [4]
R / W
C000
0000
0x002C
float
R / W
SCL
Normalization start value: Input 1
-1999...9999
0
0x002E
float
R / W
SCH
Normalization end value: Input 1
-1999...9999
100
0x0030
float
R / W
SCL2
Normalization start value: Input 2
-1999...9999
0
0x0032
float
R / W
SCH2
Normalization end value: Input 2
-1999...9999
100
0x0034
float
R / W
SPL
Start value setpoint limitation
-1999...9999
0
0x0036
float
R / W
SPH
End value setpoint limitation
-1999...9999
100
0x0038
float
R / W
OFF1
Offset input 1
-1999...9999
0
0x003A
float
R / W
OFF2
Offset input 2
-1999...9999
0
0x003C
float
R / W
OFF3
Offset input 3
-1999...9999
0
0x003E
float
R / W
HYST
Hysteresis of limit comparator
0...9999
1
0x0040
float
R / W
df1
Filter time constant input 1
0.0...100.0
1.0
0x0042
float
R / W
dF3
Filter time constant input 3
0...1440
1278
0x0044
float
R / W
dtt
Bus detection timer
0...7200 *
30
0x0046
float
R / O
oLLo
Start value actual value limit
-1999...9999
-1999
0x0048
float
R / O
oLHi
End value actual value limit
-1999...9999
9999
* Timer = 0 means switched off
This parameter can only be changed via the management system
Process data
Parameter level
Configuration level