beautypg.com

Siemens RS-485 User Manual

Page 8

background image

8/14

Siemens Building Technologies

CC1A7865.1en

HVAC Products

31.10.2002

Writing n words

Slave

address

Function

0x10

Address

of first

word

Number of

words

Number of

bytes

(max. 2)

Word

value(s)

Check-

sum

CRC16

1 byte

1 byte

2 bytes

2 bytes

1 byte

x byte(s)

2 bytes

Slave address

Function 0x10

Address of

first word

Number of

words

Checksum

CRC16

1 byte

1 byte

2 bytes

2 bytes

2 bytes

Write switch-on threshold (Hys1 = -10)
Word address = 0x0018

Instruction:

0B

10

00

18

00

02

04

00

00

C1

20

CRC16

Reply:

0B

10

00

18

00

02

CRC16

The high byte must be transmitted first.

Example:

Configuration code C111:

“9030“

MOD bus:

0B10 0024 00 02 04 0903

The following explanations apply under the condition that the master works with the
IEEE-754 format. Before transmitting a value, the bytes must be exchanged in a way
that the order corresponds to the presentation for the MOD bus (see illustration below).

M-23 bit normalized mantissa
E-exponent (complement to base 2)
S-Sign-bit; 1 = negative, 0 = positive

MOD-Bus

Master

Re

ad

Wr

ite

MMMMMMMM MMMMMMMM

SEEEEEEE

EMMMMMMM

EMMMMMMM

SEEEEEEE

MMMMMMMM MMMMMMMM

(IEEE 754)

7865z13e/1102

Example:
Transmission of decimal value “550“:

MOD bus:

0x80, 0x00, 0x44, 0x09

Following is a description of all process values (variables) with their addresses, data
type and type of access.

Where:

R / O

Read only access

R / W

Read and write access

float

Float value (4 bytes / 2 words)

word

Integer (2 bytes / 1 word)

The process values are subdivided into logic areas.

Instruction

Reply

Example

Data type “char“

Data type “float“