beautypg.com

Siemens RS-485 User Manual

Page 12

background image

12/14

Siemens Building Technologies

CC1A7865.1en

HVAC Products

31.10.2002

Description of operating modes

Parameter «RemoteStatus» is used to switch between the operating modes «LOCAL»,
«REMOTE SETPOINT» and «FULLY REMOTE». The change is always accomplished
via the MOD bus.
In the event the master fails or communication is lost, the RWF40... will switch to oper-
ating mode «LOCAL». The time for detecting a failure is set via the interface.

Remote
parameter

Default after
«Power-up»

REM

Operating mode «LOCAL», «REMOTE SETPOINT» or
«FULLY REMOTE»

= 0

SPR

Setpoint remote

= SP1

RHYS1

Switch-on threshold remote

= Hys1

RHYS2

Lower switch-off threshold remote

= Hys2

RHYS3

Upper switch-off treshold remote

= Hys3

ROFF

Controller ON (0) / OFF (1) in operating modes
«REMOTE SETPOINT» and «FULLY REMOTE»

= 0 ¹

)

RSTEP

Number of control cycles (opening / closing) (FULLY
REMOTE)

= 0 ²

)

RK1

Release of burner (FULLY REMOTE)

= 0 ³

)

RK2

Controlling element opens (FULLY REMOTE)

= 0 ³

)

RK3

Controlling element closes (FULLY REMOTE)

= 0 ³

)

RK6

Value of «K6» in operating modes «SETPOINT
REMOTE» and «FULLY REMOTE»

= 0

RY

Degree of modulation for the analog output (FULLY
REMOTE) in %

= 0

¹

)

Controller active

²

)

No travel command (K2 + K3 = deenergized)

³

)

When the operating mode changes (e.g. LOCAL

® FULLY REMOTE), the relay

information and the degree of modulation will be predefined, depending on the
operating state of the plant.

Dtt

Bus detection timer (value will also be maintained after a power failure)

The remote parameters are stored in RAM and will no longer be available after a power
failure.
After «Power-up», the default values will be used.

General

RAM parameter for re-
mote operation