Siemens RS-485 User Manual
Page 10
10/14
Siemens Building Technologies
CC1A7865.1en
HVAC Products
31.10.2002
Address
Data
type
Access
Parameter
Value range
Default
value
0x0300
word [13]
R / O
Device data
0x0300
char SWVersion [11+1]
Software version
0x0306
char VDNNr [13+1]
VdN number
Address
Data
type
Access
Parameter
Value range
Default
value
0x0400
float
R / O
TEMP
Actual value E3 (unfiltered)
0x0500
word
R / W
REM
Activation remote operation
0...2 *
0
0x0501
word
R / W
ROFF
Controller OFF in REMOTE
SETPOINT
0...1 **
0
0x0502
float
R / W
RHYS1
Switch-on threshold REMOTE
0...-1999
HYS1
0x0504
float
R / W
RHYS2
Switch-off threshold bottom
REMOTE
0...RHYS3
HYS2
0x0506
float
R / W
RHYS3
Switch-off threshold top REMOTE
0...9999
HYS3
0x0508
float
R / W
SPR
Setpoint REMOTE
SPL...SPH
SP1
0x050A
word
R / W
RK1
Burner control remote operation
0...1
0
0x050B
word
R / W
RK2
Relay K2 remote operation
0...1
0
0x050C
word
R / W
RK3
Relay K3 remote operation
0...1
0
0x050D
word
R / W
RK6
Relay LK remote operation
0...1
0
0x050E
word
R / W
RSTEP
Step control remote operation
-100...100
0
0x050F
float
R / W
RY
Positioning output remote
operation
0...100
0
*
0 = local
**
1 = controller OFF
1 = remote setpoint
2 = fully remote
Device data
Remote operation