Siemens RS-485 User Manual
Page 6
6/14
Siemens Building Technologies
CC1A7865.1en
HVAC Products
31.10.2002
Checksum (CRC16)
The checksum (CRC16) is used to detect transmission errors.
If the evaluation reveals an error, the relevant device will not respond.
CRC = 0xFFF
CRC = CRC XOR ByteOfMessage
For (1 to 8)
CRC = SHR (CRC)
if (flag to the right = 1)
then
CRC = CRC XOR
0xA001
else
while (not all ByteOfMessage edited)
+
The low byte of the checksum will be transmitted first.
Data query:
Reading 2 words from address 6 (CRC16 = 0x24A0)
0B
03
00
06
00
02
A0
24
CRC16
Reply:
(CRC16 = 0x6105)
0B
03
04
00
00
42
C8
61
05
Word 1
Word 2
CRC16
The following functions for the device will be available:
Function number
Function
0x03 / 0x04
Reading n words (n
£ 12)
0x06
Writing 1 word
0x10
Writing n words (n
£ 2)
Calculation
Example
See also other documents in the category Siemens Mobile Phones:
- A75 (16 pages)
- SXG75 (166 pages)
- CX65 (75 pages)
- A50 (77 pages)
- C30 (31 pages)
- A65 (58 pages)
- SL75 (139 pages)
- A35 (43 pages)
- M75 (153 pages)
- SX1 (103 pages)
- C55 (110 pages)
- M55 (140 pages)
- SL45 (86 pages)
- S65 (145 pages)
- S75 (72 pages)
- CF75 (150 pages)
- CFX65 (77 pages)
- AX75 (28 pages)
- C75 (144 pages)
- M65 (142 pages)
- CX75 (152 pages)
- ST60 (89 pages)
- U15 (188 pages)
- CF62 (122 pages)
- C45 (82 pages)
- Xelibri 8 (36 pages)
- Xelibri 7 (31 pages)
- SL45i (90 pages)
- SL42 (96 pages)
- Xelibri 3 (34 pages)
- ST55 (88 pages)
- SL55 (137 pages)
- C62 (67 pages)
- C62 (69 pages)
- Xelibri 6 (30 pages)
- M50 (96 pages)
- Xelibri 2 (31 pages)
- Xelibri 4 (31 pages)
- A57 (37 pages)
- A36 (43 pages)
- Xelibri 1 (31 pages)
- Xelibri 5 (30 pages)
- C70 (144 pages)
- Gigaset SL 740 (76 pages)
- Mobile Phone C35i (2 pages)