(3-2) Alarm Code : E07/P04/P05/P20/P27

Troubleshooting Serial Communication

1. Turn off the power and wait until the power lamp (LED)

of the outdoor unit controller is turned OFF.

2. Disconnect the cable from the terminal 3 on the indoor

unit terminal strip. (Fig. 7)

Defect in the indoor unit

P.C. board

Defect in the outdoor unit

P.C. board

1. Turn ON the power and operate the system using the

remote controller or the operation button on the indoor unit.

2. Perform the self-diagnosis five seconds after the operation

start.

1. Turn off the power and wait until the power lamp (LED)

of the outdoor unit controller is turned OFF.

2. Disconnect the cable from the terminal 3 on the Outdoor

unit terminal strip. (Fig. 6)

Defect in the inter-unit

cable

1. Turn ON the power and operate the system using the

remote controller or the operation button on the indoor unit.

2. Perform the self-diagnosis five seconds after the operation

start.

What is the latest self-diagnosis result ?

What is the latest self-diagnosis result ?

1

2

4

3

5

6

1

2

3

Outdoor Unit

Fig. 6

Power

Indoor Unit

1

2

4

3

5

6

1

2

3

Power

Fig. 7

Outdoor Unit

Indoor Unit

Alarm Code : E07/P04/P05/

P20/P27

Alarm Code : E05

Alarm Code : E07/P04/P05/

P20/P27

Alarm Code : E05