Refrigerant flow diagram, 1. refrigerant flow diagram, Insulation of refrigerant tubing – Sanyo DC INVERTER SPLIT SYSTEM AIR CONDITIONER C1271 User Manual
Page 28

Wide tube
Narrow tube
Heat exchanger
Indoor unit
Strainer
O.D.
3/8"
(9.52 mm)
O.D.
1/4"
(6.35 mm)
4. REFRIGERANT FLOW DIAGRAM
4-1. Refrigerant Flow Diagram
Indoor Unit
XS1271 & PNR-XS1872
Outdoor Unit C1271
CL1271
Insulation of Refrigerant Tubing
Because capillary tubing is used in the outdoor unit, both the
wide and narrow tubes of this air conditioner become cold. To
prevent heat loss and wet floors due to dripping of
condensation, both tubes must be well insulated with a
proper insulation material. The thickness of the insulation
should be a min. 5/16"(8 mm).
After a tube has been insulated,
never try to bend it into a narrow
curve because it can cause the tube
to break or crack.
Wide tube
Thickness:
Min. 5/16"(8 mm)
Insulation
Narrow tube
Thickness:
Min. 5/16"(8 mm)
IMPORTANT
CAUTION
Compressor
Accumulator
Wide tube
service
valve
Narrow
tube
service
valve
Heat exchanger
Muffler
Cooling cycle
Outdoor unit
Electric
expansion
valve
M
Muffler
H.P.
High pressure
switch
28