beautypg.com

Zone relay module - 4xzm – System Sensor PDRP-1002 Series User Manual

Page 26

background image

2. Installation

Optional Modules

26

PDRP-1002 Instruction Manual PN 51135:B0 04/06/01

Zone Relay Module - 4XZM

Relay #1 through #4 on this module have specific functions based on the configuration of DIP switches
#1 and #2 on the control panel. See “Zone Relay Module Configuration” on page 30 for a more detailed
explaination of the conditions that will activate each relay under the different DIP switch setings.

For non-latching (silenceable) relay operation, cut the jumper “LATCH”. If this jumper is left intact, the
relays will latch upon activation. To disconnect relays entirely, slide the disable switch to the right.

Note: If any dry contacts are to be used as nonpower-limited circuits, write this on the Protected Premises Unit label,
located on the door of the control panel.

Figure 16 Wiring the Zone Relay Module

The wiring of this module must follow the requirements specified under "Power-limited Wiring
Requirements" on page 17.

• If this module is used to drive both nonpower-limited and power-limited circuits, skip one set of

dry contacts to maintain the required separation between circuit types.

• If this module is used to drive both nonpower-limited and power-limited relays that are next to each

other, refer to the figure below which shows the one allowable arrangement.

Figure 17 Mixing Power-Limited and Nonpower-Limited Circuits

T B1

LAT C H

D IS ABL E

J2

Disable Switch

“Latch” Jumper

4X

Z

M

F

.cdr

Power-Limited
Circuit

Nonpower-Limited
Circuit

MS

44-

-4xzm

f1.cdr

No Connection