Horizontally vented, category iii - figure 15, Standard combustion – Sterling TUBULAR GAS FIRED DIRECT SPARK PROPELLER UNIT HEATERS GG-30 User Manual
Page 21

21
HORIZONTALLY VENTED, CATEGORY III - Figure 15
Observe the following precautions 
when venting the unit:
1. Use fl ue pipe of the same size 
as the fl ue connection(s) on the 
gas unit heater, 4" (102mm). All 
heaters must be vented with a 
single or double wall pipe listed 
for category III positive pressure 
vent systems. 
Type B double wall pipe can be
used with limitations as shown in 
Figure 15B. As illustrated, a 
single 5 foot (1.52m) section of 
Type B vent pipe with a draft 
hood connector may be used 
between the appliance vent 
connection and the vent terminal. 
Use Metalbestos Type B gas 
vent with a Metalbestos 4RV-DH 
draft hood connector, or, an 
Amerivent Type B gas vent with 
an Amerivent 4EDC draft hood 
connector.
2. Each unit must have an
individual vent pipe and vent 
terminal. Unit MUST NOT be 
connected to other vent systems 
or to a chimney.
3. Category
III units are limited to
a maximum of 40 feet (12.19m) 
equivalent length of vent pipe. 
Equivalent length is the total 
length of straight sections PLUS 
5 feet (1.5m) for each 90 degree 
elbow and 2.5 feet (.75m) for 
each 45 degree elbow.
4. If using a single section of Type
B vent pipe, seal the annular 
space between the inner and 
outer sections of the draft hood 
connector with a high temper-
ature silicone sealant. Use 
General Electric RTV-108, Dow-
Corning RTV-732, or equivalent 
silicone sealant with a temper-
ature rating of 500 deg. F. See 
Figure 15C. Attach the draft 
hood connector to the appliance 
vent connection with screws 
(3 minimum) and seal the joint 
with silicone sealant. Install a 
Type B vent thimble in the wall. 
Inser t the vent pipe through 
the thimble and attach it to the 
adapter on the appliance. Seal 
the joint with silicone sealant or 
two wraps of aluminum foil tape. 
Install a vent cap on the outlet 
pipe and secure with screws (3 
minimum). 
5. An Amerivent Americap or
Metalbestos vent cap must be 
supplied by the customer for 
each power vented unit. The vent 
pipe diameter must be 4 inches 
(102mm).
6. Through the wall venting for
these appliances shall not 
terminate over public walkways, 
or over an area where the 
condensate or vapor could 
create a nuisance, hazard, or 
could be detrimental to the 
operation of regulators, relief 
valves, or other equipment, see 
Figures 15A, 16 and 18.
7. The vent terminal must be at
least 3 feet (1m) above grade, 
or in snow areas, at least 3 feet 
above the snow line to prevent 
blockage by snow.
8. The vent terminal must be at
least 12 inches (305mm) from 
the exterior of the wall that 
it passes through to prevent 
degradation of the building 
materials by fl ue gasses.
9. M a i n t a i n 1 - i n c h ( 2 5 . 4 m m )
clearance between the vent 
pipe and combustible materials. 
10. Seal all vent pipe joints and
seams to prevent leakage. Use 
General Electric RTV-108, Dow-
Corning RTV-732, or equivalent 
silicone sealant with a temper-
ature rating of 500 deg.F, or 3M 
#425 aluminum foil tape (or 
equivalent). The vent system 
must be installed to prevent 
collection of condensate. Pitch 
horizontal pipes downward 1/4 
inch per foot (21mm per meter) 
toward the outlet for condensate 
drainage. Install a tee with a 
condensate drain at the low point 
of the pipe (see Figure 15A). As 
an alternate, a 3/8 inch diameter 
hole may be drilled at the low 
point of the pipe for condensate 
drainage.
11. Horizontal portions of the venting
system shall be supported at 
minimum intervals of 4 feet 
(1.2m) to prevent sagging (in 
Canada, support at 3 foot (1m) 
minimum intervals).
12. Avoid running vent pipe through
unheated spaces. When this 
cannot be avoided, insulate the 
pipe to prevent condensation 
of moisture on the walls of the 
pipe.
Door, window or 
any gravity air inlet
Forced air inlet within 10 ft.
Adjoining building or parapet
Adjacent public walkways
Minimum
Clearances for
Termination
Locations
Structure
4 feet 
below
4 feet 
horizontally
1 foot 
above
3 feet 
above
6 feet
7 feet 
above grade
Vent Systems
Termination Clearance Requirements
STANDARD COMBUSTION
- TUBULAR GAS FIRED DIRECT SPARK PROPELLER UNIT HEATERS GG-60 TUBULAR GAS FIRED DIRECT SPARK PROPELLER UNIT HEATERS GG-105 TUBULAR GAS FIRED DIRECT SPARK PROPELLER UNIT HEATERS GG-120 TUBULAR GAS FIRED DIRECT SPARK PROPELLER UNIT HEATERS GG-45 TUBULAR GAS FIRED DIRECT SPARK PROPELLER UNIT HEATERS GG-75 TUBULAR GAS FIRED DIRECT SPARK PROPELLER UNIT HEATERS GG-90
 
