S U F S E R V I C E H A N D B O O K

T R O U B L E S H O O T I N G

Technical Training Department

State Water Heaters

STC-077

22

Ashland City, Tennessee © 2004

ECO CHECK (CONTINUED)

STEP 5: CHECK FOR 24 VAC BETWEEN PIN 1 ON CN3 PLUG AND GROUND.

Condition:

• Reconnect CN3 plug to control board.
• On/Off switch is on.

Insert one meter probe into the back of CN3 plug pin 1, check for 24 VAC between here and ground
with CN3 plugged in and power on. (See illustration above for pin number locations.)

STEP 5

24 VAC FROM ECO

IF…

THEN

24 VAC is not present

make sure water temperature in tank is below 160° F, press Set/Reset button on
display panel, replace upper temperature/ECO probe if tank water temperature is
below 160 and Step 4 has been performed and results were successful.

24 VAC is present

continue to Step 6.