Page 5

background image

- 5 -

3. Wiring and Setting

2-3. Applicable solenoid valve series

SI unit

Valve series

EX120

VQ1000, VQ2000

EX121

VQ1000, VQ2000, SX3000, SX5000

EX122

SY3000, SY5000

EX124U/D

VQ2000, VQ4000, VQ5000

Terminal resistance

Node

Node

Node

Node

Node

Node

Node

Node

Node

Branch

line

Branch

line

Branch

line

T branch

Branch line

branch

Main line

Multi branch

Terminal resistance

Communication

distance

Baud rate

Total length of

trunk

Length of

branch line

Total length of

branch line

500 kbps

100m or less

39m or less

250 kbps

250m or less

78m or less

Thick cable

125 kbps

500m or less

6m or less

156m or less

Thin cable

Common

100m or less

――――――

Terminal resistance

121 ohm (1/2W)

Length of cable

3-1.Connection type
DeviceNet can be connected by T branch, Multi branch, Branch line branch and Multi drop. Total
extension length of trunk and Branch line is different for different Baud rate and thickness of
communication cable.

SI unit I/O data (Receiving and sending data of polled command)

Item

Output(Poll request)

Input(Poll response)

Occupied byte

2 byte

(Solenoid valve output)

2 byte

Address +0

Output No. 0 to 7

Sending/

receiving data

Address +1

Output No. 8 to 15

Bit of each output data and corresponding solenoid valve no.

Offset

MSB

LSB

0

No.7

No.6

No.5

No.4

No.3

No.2

No.1

No.0

1

No.15 No.14 No.13 No.12

No.11

No.10

No.9

No.8

SMC CORPORATION

Doc.No.EX

##

-OME0015

*) Mapping method of sending / receiving data is different by PLC.

For further information, refer to the manual for PLC master (scanner)