Marley

/

Sigma F Series

Cooling Tower

/

Engineering Data : Support

6

A

SPACES AT 4'-0" =

L

6" MIN

TYP

SUMP

SEE NOTE 7

OPTIONAL PARTITION WALL

FOR INDIVIDUAL CELL OPERATION

B

B

P

AIR INLET FACE

AIR INLET FACE

CASED ENDW

ALL F

ACE

CASED ENDW

ALL F

ACE

W

IN T

O IN OF CURB W

ALLS

PLAN

1'-6"

1'-0"

TOP OF BASIN CURB

OPERATING WATER

LEVEL RECOMMENDED

SECTION B

1'-6"

TOP OF BASIN CURB

1'-4"

6" MIN

TOP OF PARTITION WALL

SECTION P

NOTE

1 Use this bulletin for preliminary layouts only. Do not use

for construction. Obtain current drawings from your Marley

representative.

2 Tower weight is total wet operating weight of tower only ex-

cluding water in the concrete basin.

3 Purchaser to design, construct and furnish concrete basin

complete to suit the general dimensions of current Marley

drawings.

4 Last number of model indicates number of cells. Change as ap-

propriate for your selection. Primary engineering data is per cell.

5 All anchor bolts complete with nut and washer will be furnished

by others. Bolts are

3

4

" diameter with 1

1

2

" all thread projection.

Material should be stainless steel.

6 Maintain no less than 2'-0" of clear space at tower endwalls for

construction purposes. Louvered faces must have unobstruct-

ed air supply. If obstructions exist nearby, consult your Marley

representative.

7 Purchaser must design, construct, and furnish sump(s) and

overflow(s) to suit requirements. The sump should be designed

according to the pump manufacturer's recommendations.

Tower

Model

Note 4

Dimensions

Operating Weight lb

A

W

L

Single Fan Cell

Each Cell Add

F1211

4

26'-4"

16'-0"

39220

35920

F1221

4

28'-4"

16'-0"

41460

38160

F1231

5

28'-4"

20'-0"

48200

44860

F1241

6

28'-4"

24'-0"

55300

51980

F1251

6

32'-4"

24'-0"

61260

57880

F1261

7

32'-4"

28'-0"

68280

64800