Marley

/

Sigma F Series

Cooling Tower

/

Engineering Data: Energy Management

10

CAUTION

The cooling tower must be located at such distance and
direction to avoid the possibility of contaminated tower
discharge air being drawn into building fresh air intake
ducts. The purchaser should obtain the services of a
Licensed Professional Engineer or Registered Architect to
certify that the location of the tower is in compliance with
applicable air pollution, fire, and clean air codes.

Cooling towers are usually selected to produce a specific

cold water temperature at the higher summertime wet-bulb

temperatures. During the remainder of the year, the cooling

tower is capable of producing much colder water. Unless your

system will benefit from the coldest possible water tempera-

ture, you should consider controlling cold water temperatures

to higher levels. You’ll also save energy by using such control.

For greater insight on cold water temperature control, please

read “Cooling Tower Energy and its Management”, Techni-

cal Report #H-001A, available from your Marley sales represen-

tative or on the web at spxcooling.com.

Always control leaving water temperature by manipulating

the quantity of air that the fan moves through the tower. Vary-

ing the quantity of water flow is not normally recommended

and can be harmful in freezing weather. You can alternately

start and stop single-speed motors to maintain water tempera-

tures within an acceptable range. However, exceeding a total

acceleration time of 30 seconds per hour can overheat the mo-

tor, causing the insulation to fail. Limiting the number of motor

starts, on the other hand, can produce significant variations in

the temperature of the water delivered to the process.

Increased flexibility can simplify your operating procedures

and save you money in the long run, both on operation and on

maintenance. Here are two of the more popular options.

Two-Speed Motors

Two-speed motors improve operating flexibility by increas-

ing the number of potential operating modes. Users in northern

climates will find that the tower can carry winter loads at

half-speed; reducing fan power requirements by 85+% during

that time. Two-speed motors also help to control icing during

wintertime operation. See Marley Technical Report #H-003,

“Operating Cooling Towers During Freezing Weather,”

available from your Marley sales representative or on the web

at spxcooling.com.

Normally, two-speed motors are provided in 1800/900 RPM,

single winding configuration, which is the least expensive two-

speed option. They are also available in other combinations

including the more expensive double winding.

Variable Speed Fan

Frequency modulation devices work well on induced draft,

propeller fan cooling towers such as the Sigma. However, their

design must include the capability to lock out any critical fan

speeds and the very low fan speed ranges.

Marley VFD drive systems are designed to combine abso-

lute temperature control with ideal energy management. The

cooling tower user selects a cold water temperature and the

drive system will vary the fan speed to maintain that tempera-

ture. Precise temperature control is accomplished with far

less stress to the mechanical equipment components. The

improved energy management provides fast payback. Indeed,

many utilities offer generous rebates for users having installed

VFD drives.