beautypg.com

SPX Cooling Technologies Evaporative Air Cooler FSIG-TS-08A User Manual

Page 22

background image

Specifications

Marley

/

Sigma F Series

Cooling Tower

/

Specifications: Options

22

Specification Value

Plenum Walkway:

9.1 Add the following to the end of this

paragraph: Provide a 30" (762 mm)

minimum wide walkway extending

from one endwall access door to the

other through the length of the tower.

Walkway shall be constructed of

fiberglass components with a nonskid

surface on floor members, and the top

of the walkway shall be above the cold

water basin overflow level. If the cold

water basin is deeper than 4'-0" (1.22

m), the walkway shall be equipped

with fiberglass guardrails.

Ladder Extension:

9.4

Add the following paragraph in the

Access and Safety section: Provide

a ladder extension for connection to

the base of the ladder attached to

the tower casing. This extension shall

be long enough to rise from the roof

(grade) level to the base of the tower.

Anchorage and lateral bracing of the

ladder extension shall be by others.

Ladder Safety Cage:

9.3

Add the following to the end of this

paragraph: A heavy gauge galvanized

steel safety cage shall surround the

ladder, extending from a point approxi-

mately 7'-0" (2.13 m) above the base

of the ladder to the top of the guardrail

surrounding the fan deck.

Hot Water Basin Covers:

7.4 Add the following paragraph in

the Hot Water Distribution System

section: The distribution basins shall

include stainless steel covers. These

covers shall be designed to withstand

40 psf (1.92 kPa) live load, and shall be

easily removable for maintenance.

This option permits freedom of movement for inspection or main-

tenance within the tower without the need for wading boots or

tower drainage. It also helps prevent maintenance personnel from

damaging submerged accessories in the cold water basin (such

as sump screens, probes, basin heaters, etc.).

The need for guardrails where basins are deeper than 4’-0” (1.22

m) is an OSHA requirement.

Many towers are installed such that the base of the tower is

2’-0” (610 mm) or more above the roof or grade level. This makes

it difficult to get up to the base of the attached ladder. The ladder

extension alleviates this problem. Marley's ladder extensions are

available in standard 5’-0” (1.52 m) and 11’-0” (3.35 m) lengths,

and will be field-cut to fit.

To meet OSHA standards, towers whose fan decks are 20’-0”

(6.10 m) or more above roof or grade, and which are equipped

with ladders, are required to have safety cages surrounding the

ladders. Their use on lower elevation towers is a matter of choice.

These covers are designed to keep leaves and debris out of the

circulating water system. They also serve to suppress algae for-

mation by shielding the incoming hot water from direct sunlight.