beautypg.com

SPX Cooling Technologies Evaporative Air Cooler FSIG-TS-08A User Manual

Page 25

background image

Specifications

Marley

/

Sigma F Series

Cooling Tower

/

Specifications: Options

25

Specification Value

Fan Motor Variable Speed Drive:

Marley All Weather ACH550 System

6.4 Add the following paragraph in the

Mechanical Equipment section when

VFD is used with customers Building

Management System: A complete UL

listed Variable Speed Drive system in

a NEMA 1 indoor, NEMA 12 indoor or

NEMA 3R outdoor enclosure shall be pro-

vided. The VFD shall use PWM technol-

ogy with IGBT switching and integrated

bypass design. VFD out put switching

shall not cause mechanical issues with

gearbox teeth or drive shafts. The VFD

shall catch a fan spinning in the reverse

direction without tripping. The panel shall

include a main disconnect with short

circuit protection and external operating

handle, lockable in the off position for

safety. The VFD system shall receive a

speed reference signal from the Building

Management System monitoring the

tower fluid temperature. As an option

to receiving the speed reference signal

from a building management system, the

drive must have the capability to receive

a 4-20 ma temperature signal from an

RTD transmitter. The VFD shall have an

internal PI regulator to modulate fan

speed maintaining set point temperature.

The drive's panel display shall be able

to display the set-point temperature and

cold-fluid temperature on two separate

lines. The bypass shall include a complete

magnetic bypass circuit and with capabil-

ity to isolate the VFD when in the bypass

mode. Transfer to the bypass mode shall

be manual in the event of VFD failure.

Once the motor is transferred to the

by-pass circuit the fan motor will run at

constant full speed. The bypass circuit

will not modulate ON and OFF based on

fluid temperature. The application must

be able to handle very cold fluid tempera-

tures while the VFD is in a by-pass mode.

Operator controls shall be mounted on

the front of the enclosure and shall con-

sist of start and stop control, bypass/

VFD selection, Auto/Manual selections,

manual speed control. To prevent heating

problems in the fluid cooloer fan motor

and to assure proper gear reducer lubrica-

tion the VFD system shall de energize the

motor once 25% motor speed is reached

Marley VFD drive systems are designed to combine absolute

temperature control with ideal energy management. The cool-

ing tower user selects a cold water temperature and the drive

system will vary the fan speed to maintain that temperature.

Precise temperature control is accomplished with far less stress

to the mechanical equipment components. The improved energy

management provides fast payback. Indeed, many utilities offer

generous rebates for users having installed VFD drives.