Plan elevation – SPX Cooling Technologies Evaporative Air Cooler FSIG-TS-08A User Manual
Page 5
Marley
/
Sigma F Series
Cooling Tower
/
Engineering Data : Support
5
A
SPACES AT 4'-0" =
L
W
OVERALL OF B
ASIN
SUMP
OVERFLOW
MAKEUP
VALVE
INTERMEDIATE BEAM
AIR INLET FACE
AIR INLET FACE
CASED ENDW
ALL F
ACE
CASED ENDW
ALL F
ACE
PRIMARY SUPPORT
BEAM
PLAN
ELEVATION
NOTE
1 Use this bulletin for preliminary layouts only. Do not use
for construction. Obtain current drawings from your Marley
representative.
2 Operating weight is total wet weight including stainless steel
collection basin with 6" (recommended operating water level)
of water.
3 Purchaser to design, construct and furnish supporting steel
complete with
13
⁄
16
" diameter holes for anchor bolts to suit the
general dimensions of current Marley drawings.
4 Last number of model indicates number of cells. Change as ap-
propriate for your selection. Primary engineering data is per cell.
5 Maintain no less than 2'-0" of clear space at tower endwalls for
construction purposes. Louvered faces must have unobstruct-
ed air supply. If obstructions exist nearby, consult your Marley
representative.
2
1
/
4
" MAX.
NORMAL
GAGE
COL. & ANCH. BOLT
CL
SECTION
Tower
Model
Note 4
Dimensions
Operating Weight lb
A
W
L
Single Fan Cell
Each Cell Add
F1211
4
26'-6"
16'-0"
55810
51510
F1221
4
28'-6"
16'-0"
59300
54920
F1231
5
28'-6"
20'-0"
70180
65760
F1241
6
28'-6"
24'-0"
81410
77020
F1251
6
32'-6"
24'-0"
91070
86450
F1261
7
32'-6"
28'-0"
102800
98090