9710 System Assurance Guide

MR0012J

Table A-3. Optional Power Distribution Unit (PDU) Specifications

Power cable

U.S./Canada:
120 VAC UL/CSA power cable

International:
200–240 VAC HAR power cable

Input voltage range

Nominal voltage

100–254 VAC

120 or 240 VAC

Power configuration

U.S./Canada:
Single phase 120 VAC, 47–63 Hz, 6 A Service, 3-wire

International:
Single phase 200–240 VAC, 47–63 Hz, 3 A Service, 3-
wire

Power consumption

38 W

Maximum heat
output

128 Btu/hr

Table A-4. LSM Environmental Specifications

Temperature
Operating
Storage
Shipping

15° to 32°C (59° to 90°F)
10° to 40°C (50° to 104°F)
10° to 40°C (50° to 104°F)

Relative Humidity
Operating
Storage
Shipping

20% to 80% (noncondensing)
10% to 95% (noncondensing)
10% to 95% (noncondensing)

Wet Bulb Maximum
Operating
Storage
Shipping

29.2°C (84.5°F)
35°C (95°F)
35°C (95°F)

Altitude
Operating
Storage
Shipping

0 to 3.05 km (0 to 10,000 ft)
0 to 3.05 km (0 to 10,000 ft)
0 to 15.24 km (0 to 50,000 ft)