Standard setting, Battery voltage, Auxiliary contact – Studer Innotec XPC 1112 User Manual
Page 19: Reset value, Battery voltages and absorption time, Table of voltage and timing threshold, Set the voltage and timing threshold, Tandard setting, Eset value, Attery voltages and absorption time

STUDER INNOTEC
XP-COMPACT
6.1 Standard
setting
The XP-COMPACT is delivered with the following default setting:
6.1.1 Battery
voltage
Low voltage
11.6V / 23.2V / 46.4V
Float Charge
13.5V / 27.0V / 54.0V
End of Charge Voltage
14.4V / 28.8V / 57.6V
Equalization
15.3V / 30.6V / 61.2V
Absorption
Time:
2
Hours
6.1.2 Auxiliary
contact
Active in case of defect or manual turn off with the LED 10/11/12/13
6.2 Reset
value
When the XP-COMPACT is to be connected to a battery or after an interruption (RESET), it is al-
ways programmed with these standard settings. 
In order to get to these settings during operation you must press the three Push Buttons 20/21/22 
simultaneously for a minimum of 2 seconds. 
6.3 Battery voltages and absorption time
The voltage levels (low voltage, float charge, end of charge and equalization) and the duration of 
the absorption charge can be changed. 
The display of these voltages and the times in the program mode are in accordance with the dia-
gram shown below: 
6.3.1 Table of voltage and timing threshold 
 
 
Low voltage 
LED 13 
Float Charge 
LED 12 
Absorption 
LED 11 
Equalization 
LED 10 
Absorpt. time 
LED 10->13 
LED 12V 24V 48V 12V 24V 48V 12V 24V 48V 12V 24V 48V 
14 12.0 24.0 48.0 13.7 27.4 54.8 15.0 30.0 60.0 15.5 31.0 62.0 4 
h
15 11.8 23.6 47.2 13.6 27.2 54.4 14.8 29.6 59.2 15.4 30.8 61.6 3
h
16
11.6 23.2 46.4 13.5 27.0 54.0 14.6 29.2 58.4 15.3 30.6 61.2 2
h
17 11.4 22.8 45.6 13.4 26.8 53.6 14.4 28.8 57.6 15.2 30.4 60.8 1
h
18 11.2 22.4 44.8 13.3 26.6 53.2 14.2 28.4 56.8 15.1 30.2 60.4 0
–
1Min.
The heavy printed values show the standard settings.
6.3.2 Set the voltage and timing threshold 
The programming is done in accordance with the following steps: 
Push and hold down, the Push Button 21 (Program) and the Push Button 19 (Change status) for 
minimum 2 seconds simultaneously. 
OFF
Over Temp.
Overload
ON/OFF
(Select)
(Change status)
Battery
Low/High
RESET
ALARM
15
16
17
18
19
21
13
12
11
10
20
14
With the Push Button 20 (select) select with of the 
battery level and the absorption time to be changed. 
 
These four red 
LED show the function set:
Low voltage
LED 13
Float charge
LED 12
Absorption (End of charge) LED11 
Equalization 
LED
10
Absorptions Time
LED 10/11/12/13
 
With the Push Button 19 (Change status) set the 
desired parameter (voltage or the time) to modify 
(LED 14/15/16/17/18). Push Button 19 (Change 
status) to set the desired value according to the 
User manual
XP-COMPACT V2.0 E