Standard setting, Battery voltage, Auxiliary contact – Studer Innotec XPC 1112 User Manual

Page 19: Reset value, Battery voltages and absorption time, Table of voltage and timing threshold, Set the voltage and timing threshold, Tandard setting, Eset value, Attery voltages and absorption time

background image

STUDER INNOTEC

XP-COMPACT

6.1 Standard

setting

The XP-COMPACT is delivered with the following default setting:

6.1.1 Battery

voltage

Low voltage

11.6V / 23.2V / 46.4V

Float Charge

13.5V / 27.0V / 54.0V

End of Charge Voltage

14.4V / 28.8V / 57.6V

Equalization

15.3V / 30.6V / 61.2V

Absorption

Time:

2

Hours

6.1.2 Auxiliary

contact

Active in case of defect or manual turn off with the LED 10/11/12/13

6.2 Reset

value

When the XP-COMPACT is to be connected to a battery or after an interruption (RESET), it is al-
ways programmed with these standard settings.
In order to get to these settings during operation you must press the three Push Buttons 20/21/22
simultaneously for a minimum of 2 seconds.

6.3 Battery voltages and absorption time

The voltage levels (low voltage, float charge, end of charge and equalization) and the duration of
the absorption charge can be changed.
The display of these voltages and the times in the program mode are in accordance with the dia-
gram shown below:

6.3.1 Table of voltage and timing threshold

Low voltage
LED 13

Float Charge
LED 12

Absorption
LED 11

Equalization
LED 10

Absorpt. time
LED 10->13

LED 12V 24V 48V 12V 24V 48V 12V 24V 48V 12V 24V 48V
14 12.0 24.0 48.0 13.7 27.4 54.8 15.0 30.0 60.0 15.5 31.0 62.0 4

h

15 11.8 23.6 47.2 13.6 27.2 54.4 14.8 29.6 59.2 15.4 30.8 61.6 3

h

16

11.6 23.2 46.4 13.5 27.0 54.0 14.6 29.2 58.4 15.3 30.6 61.2 2

h

17 11.4 22.8 45.6 13.4 26.8 53.6 14.4 28.8 57.6 15.2 30.4 60.8 1

h

18 11.2 22.4 44.8 13.3 26.6 53.2 14.2 28.4 56.8 15.1 30.2 60.4 0

1Min.

The heavy printed values show the standard settings.

6.3.2 Set the voltage and timing threshold
The programming is done in accordance with the following steps:
Push and hold down, the Push Button 21 (Program) and the Push Button 19 (Change status) for
minimum 2 seconds simultaneously.

OFF

Over Temp.

Overload

ON/OFF

(Select)

(Change status)

Battery
Low/High

RESET
ALARM

15

16

17

18

19

21

13

12

11

10

20

14

With the Push Button 20 (select) select with of the
battery level and the absorption time to be changed.

These four red

LED show the function set:

Low voltage

LED 13

Float charge

LED 12

Absorption (End of charge) LED11
Equalization

LED

10

Absorptions Time

LED 10/11/12/13


With the Push Button 19 (Change status) set the
desired parameter (voltage or the time) to modify
(LED 14/15/16/17/18). Push Button 19 (Change
status) to set the desired value according to the

User manual

XP-COMPACT V2.0 E