14

Align the legs of the draft hood with the slots provided.

Insert the legs and secure the draft hood to the water

heater’s top with the four screws provided as shown in

Figure 9. Do not alter the draft hood in any way. If you are

replacing an existing water heater, be sure to use the draft

hood supplied with this water heater.

Vent Pipe Size

It is important that you follow the guidelines in these

instructions for sizing a vent pipe system. If a transition

to a larger vent size is required, the vent transition

connection must be made at the draft hood outlet.

Vent Connectors

1. Type B, Double wall, U.L. Listed Vent Pipe.
2. Single wall Vent Pipe.
Maintain the manufacturer’s specified minimum clearance

from combustible materials when using type B double wall

vent pipe.
Vent connectors made of type B, double wall vent pipe

material may pass through walls or partitions constructed

of combustible material if the minimum listed clearance is

maintained.
Maintain a six inch minimum clearance from all

combustible materials when using single wall vent pipe.
IMPORTANT: Single wall vent pipe cannot be used for

water heaters located in attics and may not pass through

attic spaces, crawl spaces or any confined or inaccessible

location. A single wall metal vent connector cannot pass

through any interior wall.
When installing a vent connector, please note the following

(See Figures 10-12):

Install the vent connector avoiding unnecessary bends,

which create resistance to the flow of vent gases.

Install without dips or sags with an upward slope of at

least 1/4-inch per foot.

Joints must be fastened by sheet metal screws or other

approved means. It must be supported to maintain

clearances and prevent separation of joints and

damage.

The length of the vent connector cannot exceed 75% of

the vertical vent height.

The vent connector must be accessible for cleaning,

inspection, and replacement.

Vent connectors cannot pass through any ceiling, floor,

firewall, or fire partition.

It is recommended (but not mandatory) that a minimum

12 inches of vertical vent pipe be installed on the draft

hood prior to any elbow in the vent system.

IMPORTANT: Existing vent systems must be inspected for

obstructions, corrosion, and proper installation.

Chimney Connection

IMPORTANT: Before connecting a vent to a chimney,

make sure the chimney passageway is clear and free of

obstructions. The chimney must be cleaned if previously

used for venting solid fuel appliances or fireplaces. Also

consult local and state codes for proper chimney sizing

and application or, in the absence of local and state

codes, the “National Fuel Gas Code”, ANSI Z223.1(NFPA

54)-current edition.

The connector must be installed above the extreme

bottom of the chimney to prevent potentially blocking

the flue gases.

The connector must be firmly attached and sealed to

prevent it from falling out.

To aid in removing the connector, a thimble or slip joint

may be used.

The connector must not extend beyond the inner edge

of the chimney as it may restrict the space between it

and the opposite wall of the chimney (Figure 10).

LISTED LINED
CHIMNEY

2 FT. MINIMUM ABOVE ANY OBJECT
WITHIN 10FT. HORIZONTALLY

DO NOT EXTEND
VENT BEYOND EDGE
OF CHIMNEY

VENT
CONNECTOR

3 FT. MINIMUM

MAINTAIN
CLEARANCE*

SEAL

SLOPE

UP 1/4 IN.

PER FT.

MINIMUM

CHIMNEY TERMINATION VENT SYSTEM

SUPPORT
STRAP

FIGURE 10.

Do not terminate the vent connector in a chimney that has

not been certified for this purpose. Some local codes may

prohibit the termination of vent connectors in a masonry

chimney.

Vertical Exhaust Gas Vent

Vertical exhaust gas vents must be installed with

U.L. listed type B vent pipe according to the vent

manufacturer’s instructions and the terms of its listing.
It must be connected to the water heater’s draft hood by a

listed vent connector or by directly originating at the draft

hood opening.
Vertical gas vents must terminate with a listed cap or

other roof assembly and be installed according to their

manufacturer’s instructions.
Gas vents must be supported to prevent damage, joint

separation, and maintain clearances to combustible

materials (Figures 11 and 12).
IMPORTANT: This gas vent must be terminated in a

vertical position to facilitate the removal of the burnt gases.
An unused chimney flue or masonry enclosure may be used

as a passageway for the installation of a gas vent (Figure 12).
Common (combined) venting is allowable with vertical type

B vent systems and lined masonry chimneys as long as

proper draft for the water heater is established under all

conditions of operation. CAUTION: DO NOT common vent

this water heater with any power vented appliance.
Figures 10-12 are examples of vent pipe system

installations and may or may not be typical for your

specific application. Consult the “National Fuel Gas Code”,

NFPA 54, ANSI Z223.1-current edition and the guidelines

set forth by prevailing local codes.