18
Technical data
Model
XTH 3000-12 XTH 5000-24 XTH 6000-48
XTH 8000-48
Inverter
Rated battery voltage
12 V
24 V
48 V
48 V
Input voltage range
9.5 - 17 V
19 - 34 V
38 - 68 V
39 - 68 V
Continuous power @ 25 °C
2500 VA
4500 VA
5000 VA
7,000 VA
Smart boost power
3000VA
5000 VA
6000 VA
8000 VA
30 minute load @ 25 °C
3000 VA
5000 VA
6000 VA
8000 VA
5 second load @ 25 °C
3 x Pcont
Maximum load
Up to short-circuit
Maximum asymmetrical load Up
to
Pnom
Load detection (standby)
2 to 25 W
Admissible cos phi
0.1 – 1
Maximum
efficiency
93% 94% 96% 96%
Open-circuit power OFF/standby/ON 1.3W/2.2W/14W 1.8W/2.5W/18W 2.2W/3W/22W 2.2W/3.8W/26 W
Output voltage
Sine wave 230 Vac (+/-2%) / 180-245 Vac
Output frequency
50 Hz adjustable 45-65 Hz +/- 0.05% (quartz-controlled)
Harmonic distortion
<2%
Overcharge and short-circuit
Automatic disconnection then 2 startup attempts
Overheating protection
Alarm prior to disconnection and automatic restart
Battery charger
6-phase battery charger
Programmable I-U-Uo-equalisation-Uo(low)-U(periodic)
Adjustable charge current
0 - 160 A
0 - 140 A
0 - 100 A
0 - 120 A
Input current sharing system
1 - 50 A
Maximum input voltage
265 Vac
AC input voltage range
Level of detection adjustable from 150 to 230 Vac
Admissible input frequency
45 - 65 Hz
(PFC)
EN 61000-3-2
Battery control (factory value / adjustable range with RCC-02)
End of absorption
by duration: 2h / 0.25 - 18 h or by current <10A / 2 - 50 A
Absorption voltage
14.4V / 9.5-18 V 28.8V / 19-36 V
57.6V / 38 - 72 V
Periodic absorption voltage
- / 9.5 - 18 V
- / 19 - 36 V
- / 38 - 72 V
Floating voltage
13.6V / 9.5-18 V 27.2V / 19-36 V
54.4V / 38 - 72 V
Reduced maintenance voltage
- / 9.5 - 18 V
- / 19 - 36 V
-- / 38 - 72 V
Equalisation
By number of cycles ( - / - 100) or at fixed intervals ( - / 52 weeks)
End of equalisation
By duration 2h / 0.25 – 10h or by current - / 5 – 50 A
Equalisation voltage
- / 9.5 - 18 V
- / 19-36 V
- / 38 - 72 V
Low voltage disconnection
10.8V / 9.5-18 V 21.6V /19-36 V
43.2V / 38 - 72 V
Reduced floating duration
- / 0 - 32 days
Periodical absorption
- / 0 - 10 hours
Temperature compensation
-5 / 0 to-8 mV/°C/cell (optional BTC-01)
General data
Auxiliary contacts
2 independent contacts 16 A - 250 Vac (potential-free 3 points)
Maximum transfer relay current
50 A
Maximum transfer time
0-15 ms
Weight
34
kg 40
kg 42
kg 46
kg
Dimensions: H x W x D [mm]
230x300x500
Protection degree
IP20
Conformity
EN 61000-6-1, EN 61000-6-3, EN 55014, EN 55022, EN 61000-3-2,
Dir. 89/336/EEC, LVD 73/23/EEC
Operating temperature range
-20 to 55 °C
Ventilation
Forced from 45 °C
Noise level
<40 dB / <50 dB (without / with ventilation)
Warranty 2
years
Options
Battery temperature sensor:
BTS-01
Remote control and programming centre for wall mounting: RCC-02
Remote control and programming centre for panel mounting: RCC-03