beautypg.com

18 technical data – Studer Innotec XTH 5000-24 User Manual

Page 36

background image

STUDER Innotec

Xtender

Installation and operating Instructions

Xtender V1.3

Page 36

18

Technical data

Model

XTH 3000-12 XTH 5000-24 XTH 6000-48

XTH 8000-48

Inverter

Rated battery voltage

12 V

24 V

48 V

48 V

Input voltage range

9.5 - 17 V

19 - 34 V

38 - 68 V

39 - 68 V

Continuous power @ 25 °C

2500 VA

4500 VA

5000 VA

7,000 VA

Smart boost power

3000VA

5000 VA

6000 VA

8000 VA

30 minute load @ 25 °C

3000 VA

5000 VA

6000 VA

8000 VA

5 second load @ 25 °C

3 x Pcont

Maximum load

Up to short-circuit

Maximum asymmetrical load Up

to

Pnom

Load detection (standby)

2 to 25 W

Admissible cos phi

0.1 – 1

Maximum

efficiency

93% 94% 96% 96%

Open-circuit power OFF/standby/ON 1.3W/2.2W/14W 1.8W/2.5W/18W 2.2W/3W/22W 2.2W/3.8W/26 W
Output voltage

Sine wave 230 Vac (+/-2%) / 180-245 Vac

Output frequency

50 Hz adjustable 45-65 Hz +/- 0.05% (quartz-controlled)

Harmonic distortion

<2%

Overcharge and short-circuit

Automatic disconnection then 2 startup attempts

Overheating protection

Alarm prior to disconnection and automatic restart

Battery charger

6-phase battery charger

Programmable I-U-Uo-equalisation-Uo(low)-U(periodic)

Adjustable charge current

0 - 160 A

0 - 140 A

0 - 100 A

0 - 120 A

Input current sharing system

1 - 50 A

Maximum input voltage

265 Vac

AC input voltage range

Level of detection adjustable from 150 to 230 Vac

Admissible input frequency

45 - 65 Hz

(PFC)

EN 61000-3-2

Battery control (factory value / adjustable range with RCC-02)

End of absorption

by duration: 2h / 0.25 - 18 h or by current <10A / 2 - 50 A

Absorption voltage

14.4V / 9.5-18 V 28.8V / 19-36 V

57.6V / 38 - 72 V

Periodic absorption voltage

- / 9.5 - 18 V

- / 19 - 36 V

- / 38 - 72 V

Floating voltage

13.6V / 9.5-18 V 27.2V / 19-36 V

54.4V / 38 - 72 V

Reduced maintenance voltage

- / 9.5 - 18 V

- / 19 - 36 V

-- / 38 - 72 V

Equalisation

By number of cycles ( - / - 100) or at fixed intervals ( - / 52 weeks)

End of equalisation

By duration 2h / 0.25 – 10h or by current - / 5 – 50 A

Equalisation voltage

- / 9.5 - 18 V

- / 19-36 V

- / 38 - 72 V

Low voltage disconnection

10.8V / 9.5-18 V 21.6V /19-36 V

43.2V / 38 - 72 V

Reduced floating duration

- / 0 - 32 days

Periodical absorption

- / 0 - 10 hours

Temperature compensation

-5 / 0 to-8 mV/°C/cell (optional BTC-01)

General data

Auxiliary contacts

2 independent contacts 16 A - 250 Vac (potential-free 3 points)

Maximum transfer relay current

50 A

Maximum transfer time

0-15 ms

Weight

34

kg 40

kg 42

kg 46

kg

Dimensions: H x W x D [mm]

230x300x500

Protection degree

IP20

Conformity

EN 61000-6-1, EN 61000-6-3, EN 55014, EN 55022, EN 61000-3-2,

Dir. 89/336/EEC, LVD 73/23/EEC

Operating temperature range

-20 to 55 °C

Ventilation

Forced from 45 °C

Noise level

<40 dB / <50 dB (without / with ventilation)

Warranty 2

years

Options

Battery temperature sensor:

BTS-01

Remote control and programming centre for wall mounting: RCC-02
Remote control and programming centre for panel mounting: RCC-03

This manual is related to the following products: