17

Table of standard configurations

No. of

config.

Denomination / description

Units Fact.

value

Mod.

value

1107 Maximum current of the AC source

A

30

1108 Undervoltage of the empty battery

V/cell

1.93

1109 Sub-voltage of the charged battery

V/cell

1.75

1110 Restart voltage of the inverter after undervoltage of the battery

V/cell

2

1111 Automatic startup at power up

y/n

no

1112 Inverter frequency

Hz

50

1121 Maximum DC voltage for stopping the Xtender

V/cell

2.84

1126 Source assistance (Smart Boost) permitted

y/n

no

1138 Battery charge current

A

60

1139 Battery voltage correction according to the temperature

mV/°C/
cell

-5

1140 Battery maintenance voltage

V/cell

2.27

1143 Voltage 1 to allow a new battery cycle

V/cell

2.1

1144 Duration of under voltage 1 to allow a new cycle

min.

30

1145 Voltage 2 to allow a new battery cycle

V/cell

1.93

1146 Duration of under voltage 2 to allow a new cycle

sec.

180

1156 Battery absorption voltage

V/cell

2.4

1157 Duration of absorption

h

2

1159 Current at end of absorption

Adc

10

1161 Minimum interval between absorptions

h

3

1187 Sensitivity of the charge detection (100% approx.25W)

%

10

1189 Time interval between load search pulses

sec.

0.8

1190 Duration of undervoltage of battery before disconnection

min.

3

1191 Dynamic compensation for undervoltage

y/n

yes

1194 Battery adaptive low voltage allowed

o/n

non

1195 Max voltage for adaptive low voltage

V/cell

2.08

1198 Time elapsing before transfer relay opens

sec.

8

1199 ACin voltage causing the opening of the transfer relay

Vac

180

1200 Immediate open critical threshold for the transfer

Vac

50

1246 Auxiliary contact 1 activated by voltage 1 {1247} after delays

{1248}

y/n yes

1247 Voltage 1under which auxiliary contact 1 is activated

V/cell

1.95

1248 Delays on voltage 1 to activate auxiliary contact 1

min.

1

1249 Auxiliary contact 1 activated by voltage 2 {1250} after delays

{1251}

y/n yes

1250 Voltage 2 under which auxiliary contact 1 is activated

V/cell

2

1251 Delays on voltage 2 to activate auxiliary contact 1

min.

10

1252 Auxiliary contact 1 activated by voltage 3 {1253} after delays

{1254}

y/n yes

1253 Voltage 3 under which auxiliary contact 1 is activated

V/cell

2.05

1254 Delays on voltage 3 to activate auxiliary contact 1

min.

60

1255 Voltage 1above which auxiliary contact 1 is deactivated after delays V/cell

2.25

1256 Delays on voltage {1255} to deactivate auxiliary contact 1

min.

60

1258 Auxiliary contact 1 activated by power 1

y/n

yes

1259 Power 1 above which auxiliary contact 1 is activated after delays

%

120

1260 Duration of power 1 for activating auxiliary contact 1

min.

1

1261 Auxiliary contact 1 activated by power 2

y/n

yes

1262 Power 2 above which auxiliary contact 1 is activated after delays

%

80

1263 Duration of power 2 for activating auxiliary contact 1

min.

5

1264 Auxiliary contact 1 activated by power 3

y/n

no

1286 Output

voltage

Vac

230