14 elements of connexion cabinet (fig 4a) – Studer Innotec XTH 5000-24 User Manual

Page 31

background image

STUDER Innotec

Xtender

Installation and operating Instructions

Xtender V1.3

Page 31

Elem.

Description

Comment

T

Non-secured grid

Distribution to users supplied exclusively via the present grid or the
generator.
This distribution is carried out in conformity with the local standards
and regulations.

U

Public grid

The connection to the public grid imposes adherence to the local
standards and regulations at the responsibility of the installer. The
installation should, in principle, be checked and approved by an
official body.

V Automatic

earth-

neutral connection

This connection is deactivated by default. In may be used in certain
specific cases for automatically re-establishing the neutral system
type TT (TNC, TNS, TNC-S) when the Xtender is in inverter mode.
The activation is carried out via RCC-02/03 remote control
configuration {1485}. This operation may only be carried out by
qualified personnel, under the responsibility of these personnel, and in
conformity with the local standards and regulations. See 4.2.3– p.11

W

Galvanic

isolator

This device (optional) is generally used to reduce the risk of
electrolytic corrosion due to the direct current when a boat is
connected at the dock.

X Source

reversing

switch

When the installation has more than one supply source, it is
necessary to install a switching device between the sources,
simultaneously switching the neutral and the phase(s) of these
sources. In all cases this device (manual or automatic) must
guarantee interruption of the connected source before its connection
to another source.

Y Isolation

transformer

This device (optional) prevents the risk of galvanic corrosion due to
direct currents when a boat is connected at the dock.

14

Elements of connexion cabinet (Fig 4a)

Pos.

Denomination

Description

Comment

1 ON/OFF

Main switch

Main on/off switch

See chapter 7.1 - p 24.

2 Temp.

Sens Connector for the battery

temperature sensor

See chapter 6.4.2 – p. 24.
Only connect the original Studer BTS-01
sensor

3

Com.

Bus Double connector for

connecting peripherals such as
the RCC002/03 or other
Xtender units

4

O / T
(Open /
Terminated)

Switch for terminating the
communication bus.

See chapter 4.5.9 – p. 14.
The two termination switches (4) for the
communication bus both remain in
position T (terminated) except when both
connectors are in use.

5

--

3.3 V (CR-2032) lithium ion type
battery socket

Used as a permanent supply for the
internal clock. See chapter 6.2.11 - p 21.

6

--

Jumper for programming the
off/on switch by dry contact

See chapter 6.2.12 – p. 21 and fig. 8b
point (6) and (7). They are positioned at A-
1/2 and B-2/3 by default

7 REMOTE

ON/OFF

Connection terminals for dry
on/off remote connection.

See chapter 6.2.12– p. 21).
When the control via dry contact is not
being used, a bridge must be present
between the two terminals.

8 AUXILIARY

CONTACT

Auxiliary contact

(See chapter 6.2.10– p. 21)
Take care not to exceed the admissible
loads

9

--

Activation indicators for auxiliary
contacts 1 and 2

See chapter 6.2.10– p. 21