STUDER Innotec

Xtender

Installation and operating Instructions

Xtender V1.3

Page 32

Pos.

Denomination

Description

Comment

10

L1/L2/L3

Phase selection jumpers.

See chapter 6.3.1. – p.22.
Jumper default at position L1

11

+BAT

Positive pole battery connection
terminals

12

-BAT

Negative pole battery
connection terminals

Carefully read chapter 4.5 – p.12
Take care with the polarity of the battery
and when tightening the clamp.

13 AC

Input

Connection terminals for the
alternative power supply
(generator or public network)

See chapter 4.5.7 - p. 14.
Note: It is imperative that the PE terminal
be connected.

14 AC

Output

Connection terminals for the
device output.

See chapter 4.5.6 - p. 14.
Note: Increased voltages may appear on
the terminals, even in the absence of
voltage at the input of the inverter.

15

Control and display parts for the Xtender (fig. 4b)

See chapter 7.2 - p. 24.

Pos.

Denomin
ation

Description

Comments

41

ON/OFF ON/OFF button

The ON/OFF button allows the start up or complete stoppage
of the system such as it has been programmed. When there
are several units in the same system, each unit must be
started up or stopped individually using this button.

42 OFF

Light indicator
for stoppage of
the unit

When the light indicator flashes it indicates the cause of the
stoppage of the unit, its imminent stoppage or the limitation of
its rated power output according to chapter 7.2 - p.24.

43 ON

Light indicator
showing that the
equipment is in
operation

This indicator is glowing continuously when the device is
working. It flashes when the equipment is at a temporary
stop. Note: The equipment will restart automatically when the
conditions that led to the temporary stoppage have gone
away.

44 Charge Light indicator

showing that the
battery is being
charged

This indicator is glowing continuously when the charger is in
operation and has not yet reached the absorption phase.
It flashes twice during the absorption phase and once during
the maintenance phase.
If smart boost mode has been activated it is possible that this
indicator will go out temporarily when source backup is
required by users. (See chapter 6.2.6 - p. 19)

45 AC

in Light indicator

showing the
presence of
correct and
synchronised
input voltage

This indicator is glowing continuously when an alternative
voltage with correct values is present at the AC IN input (13)
of the device and the current limit {1107) set by the user has
not been reached. It flashes when this limit is reached (see
chapter 6.2.5 – p. 19).

46 AC

out Light indicator

showing the
presence of a
voltage at the
output

This indicator is glowing continuously when an alternative
voltage of 230V is present at the device output. It flashes
when the device is in “load search” mode due to the absence
of users. (See chapter 6.2.3 – p. 16)

16

Type plate elements (fig. 1b)

Pos.

Denomination

Description

Comments

31 Model

Model

32

Pnom/P30

Rated power output / power for 30 minutes