Configuring the Modbus Models
890 USE 103 00
40
3.5 Configuring the Modbus Ports
3.5.1
Connecting Power for the Configuration
Refer to the Installation chapter in this guide for connecting power to
your BM85. Connect the source of AC or DC power to the BM85. Do
not turn on the power to the BM85 until you set the Modbus port
configuration switches and connect the configuration terminal. The
switch settings will be sensed when power is applied.
3.5.2
Setting the Switches
The BM85 power should be off at this time. Switches are located on the
BM85 rear panel. Figure 10 shows the switch positions and setup.
1 2 3 4 5 6 7 8
SWITCH POSITION
1 2 3 4 5 6 7 8
PORT MODE:
CONFIGURE
RUN
CONFIGURATION PORT:
PORT 1
PORT 2
PORT 3
PORT 4
PARITY:
DISABLED
EVEN
DISABLED
ODD
BAUD RATE:
9600
2400
1200
300
UP
UP
UP
DOWN
DOWN
DOWN
UP
UP
DOWN
DOWN
UP = 1 DOWN = 2
NW–BM85–000
NW–BM85C002
NW–BM85D008
USE
UPPER
SWITCHES
USE
RIGHT
SWITCHES
NW–BM85–000 = STOP BITS:
UP = RUN APPLICATION
NW–BM85C002
NW–BM85D008 = MODE:
(LEAVE IN UP POSITION)
UP
UP
DOWN
DOWN
UP
UP
DOWN
DOWN
UP
UP
DOWN
DOWN
UP
UP
DOWN
DOWN
Figure 10
BM85 Modbus Models: Port Configuration Switches