Troubleshooting – John Deere AC-G3200i User Manual
Page 33
Operator’s Manual
33
Troubleshooting
When generator engine fails to start after several attempts, or if no electricity is available at the output socket, check
the following chart. If your generator still fails to start or generate electricity, contact your nearest John Deere dealer or
service shop for further information or corrective procedures.
Symptom
Problem
Solution
Engine will not start.
Check if engine switch is off.
Turn engine switch to the “ “
(CHOKE) position.
Fuel Tank empty.
Fill tank making sure not to overfill.
Check to make sure generator is not
If connected, turn off the power switch
connected to an appliance.
on the connected appliance and
unplug.
Check spark plug for loose spark
If loose, push spark plug cap back
plug cap.
into place.
Check spark plug for contamination.
Remove spark plug and clean
electrode.
Check engine oil level.
If the engine oil level is low, add oil
per “Pre-Operation; Engine Oil” on
page 21.
Generator has no output.
Check if the “O_Lod”, overload,
Stop the engine and check the
is indicated in the Multi Monitor.
appliance and/or generator for
overloading.
Check if the DC circuit breaker is
Depress the circuit breaker into
turned off.
ON position, after making sure the
charging current level is proper and
the battery is in the normal condition.
Check AC receptacle and DC terminals Secure connection if necessary.
for loose connection.
Check to see if engine starting was
Turn off switch on the appliance, and
attempted with appliances already
disconnect cable form receptacle.
connected to generator.
Reconnect after generator has been
started properly.