16.8 A @ 264 V AC

Minimum

22.2 A @ 200 V AC

Nominal

18.5 A @ 240 V AC

24.7 A @ 180 V AC

Maximum

-40.0 to -59.9 V DC

DC output voltage range

-54.5 V DC

Nominal

3600 W

DC output power (max.)

AC line cord (dual; 1 active, 1 standby)

4.6 m (15 ft)

Standard length

7.6 m (25 ft)

Optional length

NEMA 30A, 250V twistlock connector

Termination (domestic)

IEC 309, 32A, 250V pin and sleeve connector

Termination (intl.)

5.4 Electrical (DC Cabinets)

Two 100A DC inputs

DC service requirements

-42.0 to -59.9 V DC

DC input voltage range

-54.5 V DC

Nominal

3650 W

DC input power (max.)

Input current (@ 3600 W of power delivered to load)

61.0 A @ -59.9 V DC

Minimum

67.0 A @ -54.5 V DC

Nominal

87.0 A @ -40.0 V DC

Maximum

3600 W

DC output power (max.)

DC line cord (dual; load sharing)

7.6 m (25 ft)

Standard length

15.2 m (50 ft)

Optional length

Double-holed ring lug connector

Termination

6. Upgrade Kits

6.1 CPU-Memory Board Upgrade Kits