beautypg.com

3 electrical (ac cabinets) – IBM 600/1200 Series User Manual

Page 11

background image

Operating temperature (AC and DC systems)

4.5º to 40º C (40º to 104º F)

-200 to 6000 ft

4.5º to 35º C (40º to 95º F)

6000 to 8000 ft

4.5º to 30º C (40º to 86º F)

8000 to 10,000 ft

Short term (<72 hrs) operating temp. (DC systems only)

1.7º to 49º C (35º to 120º F)

-200 to 6000 ft

1.7º to 45º C (35º to 113º F)

6000 to 8000 ft

1.7º to 35º C (35º to 95º F)

8000 to 10,000 ft

Heat dissipation (maximum)

15,131 Btu/hr

CEC cab. (AC systems)

15,131 Btu/hr

Expansion cab. (AC systems)

12,283 Btu/hr

CEC cab. (DC systems)

12,283 Btu/hr

Expansion cab. (DC systems)

10% to 80% non-condensing

Relative humidity

12º/hr C (21.6º/hr F)

Max. rate of temp. change

Acoustical noise (per cabinet)

67 dBA

Fans at normal speed

77 dBA

Fans at full speed

5.3 Electrical (AC Cabinets)

Two 30A, single-phase AC inputs (1 active, 1 standby)

AC service requirements

AC input voltage range

200 to 240 V AC

Nominal

180 to 264 V AC

Absolute

47 to 63 Hz

AC input frequency range

82%

Efficiency (min.)

>.99 (>10% load)

Power factor

4.44 KVA

AC input power (max.)

Input current (@ 3600 W of power delivered to load)