beautypg.com

Appendices, Technical characteristics – MGE UPS Systems 1500 Tower User Manual

Page 29

background image

3400723200/AC

- Page 29

6. Appendices

Technical characteristics

(1) The upper and lower thresholds may be set using the UPS Driver software.
(2) Or 40 Hz in low-sensitivity mode (may be set using the UPS Driver software).
(3) Adjustable from 100 to 127 V using the UPS Driver software.

Output rating

AC-input power

Voltage

Frequency

Output power (operation
on battery power)

Voltage

Frequency

Battery (sealed lead-acid,
maintenance free)

Tower models

Rack models

Environment

Noise level (operation on

AC-input power)

Operating temperature

Relative humidity

(without condensation)

Pulsar Evolution

500

500 VA / 350 W

2 x 6 V - 9 Ah,

1100 Tower/1100 Rack

1100 VA / 700 W

2 x 12 V - 9 Ah,

4 x 6 V - 9 Ah

800 Tower/800 Rack

800 VA / 560 W

2 x 12 V - 7.2 Ah,

4 x 6 V - 7.2 Ah

1500 Tower/1500 Rack

1500 VA / 1000 W

3 x 12 V - 9 Ah,

6 x 6 V - 9 Ah

Single phase, 80 V to 153 V (1)

Single-phase, 120 V (3) (+ 6% / - 10%)

50/60 Hz +/- 1 Hz

<40 dBA

0 to 35° C

20 to 90%

<40 dBA

0 to 40° C

20 to 90%

47 Hz to 70 Hz (50 Hz system) or 56.5 Hz to 70 Hz (2) (60 Hz system)