Generator outputs, Generator output voltages, Voltage selector switch – Multiquip Power Whisperwatt Series 60HZ Generator DCA70USI2 User Manual
Page 26: Voltage selector switch locking button, Generator amperage, Gfci receptacle load capability
page 26 — DCa70USI2 60 hz generaTor • operaTIon anD parTS manUal — rev. #0 (06/28/11)
generatOr Outputs
generaTor oUTpUT volTageS
A wide range of voltages are available to supply voltage for
many different applications. Voltages are selected by using
the
voltage selector switch (Figure 13). To obtain some of
the voltages as listed in Table 7 (see below) will require a
fine adjustment using the
voltage regulator (VR) control
knob located on the control panel.
voltage Selector Switch
The voltage selector switch (Figure 13) is located above
the output terminal panel’s Hard Wire Hook-up Panel. It
has been provided for ease of voltage selection.
Figure 13. Voltage Selector Switch
voltage Selector Switch locking Button
The voltage selector switch has a locking button to protect
the generator and load from being switched while the
engine is running. To lock the voltage selector switch, press
and hold the red button located at the bottom of the switch.
CaUTIon
never change the position of the voltage selector
switch while the engine is running. alWaYS place
circuit breaker in the
oFF position before selecting
voltage
.
Table 7. voltages available
UvWo output
Terminal lugs
voltage Selector Switch
3-phase 240/139v position
voltage Selector Switch
3-phase 480/270v position
3Ø
line-line
208V
220V
240V
416V
440V
480V
1Ø
line-neutral
120V
127V
139V
240V
254V
277V
voltage Selector Switch Single-phase 240/120v position
1Ø
line-neutral/
line-line
120V
Line-Neutral
N/A
N/A
240V
Line-Line
N/A
N/A
generator amperage
Table 8 shows the
maximum amps the generator can
provide.
Do noT exceed the maximum amps as listed..
gFCI receptacle load Capability
The load capability of the GFCI receptacles is directly
related to the voltage being supplied at either the output
terminals or the three twist lock auxiliary receptacles.
Table 9 and Table 10 show what amount of current is
available at the GFCI receptacles when the output terminals
and twist lock receptacles are in use. Be careful that your
load does not to exceed the available current capability at
the receptacles.
Table 8. generator maximum amps
rated voltage
maximum amps
1Ø 120 Volt
155.5 X 2 amps (4 wire)
168 amps X 2 (Zigzag)
1Ø 240 Volt
78.8 amps (4 wire)
168 amps (Zigzag)
3Ø 240 Volt
168 amps
3Ø 480 Volt
84 amps
Table 9. 1Ø gFCI receptacle load Capacity
KW in Use
Twist lock (C6369)
available load
Current (amps)
1Ø 240/120V
GFCI Duplex
5-20R 120V
40.4
0
39.2
5 amps/receptacle
38.0
10 amps/receptacle
38.6
15 amps/receptacle
35.6
20 amps/receptacle
Table 10. 3Ø generator maximum amps
Kva in Use
(UvWo Terminals)
available load
Current (amps)
3Ø 240/480V
GFCI Duplex
5-20R 120V
70
0 amps/receptacle
65.8
5 amps/receptacle
61.7
10 amps/receptacle
57.5
15 amps/receptacle
53.4
20 amps/receptacle