1.8 Technical data
1.8.1 Configuration
The user can configure the card with one of the following means:
Z
Web browser
Z
Local serial link
Z
Telnet console
Z
BOOTP/DHCP
Z
Mupgrade
1.8.2 Administration
Z
Up to 50 workstations protected
Z
Up to 15 browsers connected at the same time
Z
E-mail sending configurable according to UPS alarms and transmission of a periodical report
Z
Measurement of temperature and humidity, adjustable thresholds, possibility of sending e-mails and shutting
down the installation
Z
Control of UPS on/off switching via the HTML interface
Z
Adjustment and control of PowerShare outlets via the HTML interface, sequential starting of the installation
and optimisation of backup time by shutting down non-priority systems
Z
Adjustment of date and time via NTP server - Daylight Saving Time management
Z
Protection by encrypted password.
Z
Protection by secured connection SSL and SSH
Z
Saving of logs in the non-volatile memory
Z
Automatic language detection according to browser configuration.
Z
Languages available: English / French / Spanish / German / Italian
Z
On-line help available for each page
Z
Card firmware updated via the network
Z
Card configuration deployment on your installed base through network utility (Mupgrade)
1.8.3 Network
Z
Fast ETHERNET 10/100 Mbits compatibility with auto-negotiation on the RJ45 outlet
Z
SNMP trap port modifiable (by default = 162)
1.8.4 MIB (Management Information Base)
Z
MIB IETF UPS (RFC1628) / MIB MGE V1.7
1.8.5 Environment sensor
Z
Temperature measurement from 0 to 70 °C with +/- 1°C accuracy
Z
Measurement of humidity from 0 to 100 % with +/- 6 % accuracy
Z
Min / max time-stamped function for temperature and humidity
Z
Choice of temperature readings in Celsius or Fahrenheit
Z
High and low thresholds, hysteresis and offset adjustable via Web interface
Z
Possibility of notification of status changes by e-mail, SMS or SNMP traps
Z
Position detection of 2 dry contacts (maximum sensor/contact distance: 20 m)
Z
Name and status of each configurable contact