Network
Management Cards
User Manual
T H E U N I N T E R R U P T I B L E P O W E R P R O V I D E R
Network Management Card
– User Manual
34003676EN/GA
Page
34/69
Z
Environment log interval: [from 5 to 99999 sec ]. Temperature and humidity measurement save period.
Default value = 300 sec. (only visible if the sensor is present).
Z
Environment refresh rate: [from 5 to 99999 sec]. “Environment status” page refresh rate. Default value
= 60 sec. (only visible if the sensor is present).
Z
Environment input grace period : [from 0 to 9 sec ]. Period during which a status change by one of the
inputs is not considered. Default value = 1 sec. (only visible if the sensor is present).
Z
“Reset communication” button: performs a remote reboot of the card without modifying the configuration.
This action is compulsory for consideration of any changes made on
” page. Security
of this operation is ensured by requesting Login and Password.
Z
“Fatory Reset” button: enables restoration of the default configuration of all the card’s parameters. The
TCP/IP parameters: IP address, subnet mask, gateway and BootP/DHCP value are maintained if the
“Keep TCP/IP parameters” option is selected. Security of this operation is ensured by requesting Login
and Password. Default login and Password are: MGEUPS
Note:
If any of these parameters are changed, the card must be rebooted.