Central shutdown configuration, Network management cards, User manual – MGE UPS Systems 66074 User Manual
Page 36
www.mgeups.com
Network
Management Cards
User Manual
T H E U N I N T E R R U P T I B L E P O W E R P R O V I D E R
Network Management Card
– User Manual
34003676EN/GA
Page
36/69
Z
Remove : Depending on the kind of application, the selected ones will definitively disappear from the table
as SNMP applications, or they will disappear and automatically re-subscribe as the Network Shutdown
Module application.
Z
Utility failure Test : Two alarms 'Utility failure' and 'Utility restored' spaced of 60 seconds will be sent to the
applications selected, making sure that the applications can be reached over the network.
Z
Shutdown Test : This test simulates a UPS on battery operation, it sends alarms to the selected
applications. It enables an easy check to see if the server protection works correctly.- No intervention on
the UPS is required.
- Simulated alarms will be processed by the applications selected only.
- Warning :This test will generate a REAL shutdown sequence of servers on which Network Shutdown
Module is running.
Add NMS allows to add a SNMP trap receiver as a Network Management System.
Modify NMS allows to modify a SNMP trap receiver.
Both buttons makes appear a new window where it is possible to enter the Application name, the
Hostname or IP Address, the Trap community and the severity.
Z
Trap community indicates the name of the SNMP community
For more details, read the MIB description document: 34003627zj
3.5.4 Central Shutdown Configuration
Click the “Notified Application” section in the menu then in “Configuration”.