generatOr shut-dOWn prOcedures

2. Place the engine speed control switch (Figure 51) in

the Start/Idle position (down).

Figure 51. Engine Speed Control Switch

Start Idle Position

3. Let the engine cool by running it at low speed for 3-5

minutes with no load applied.

4. Place the ignition switch (Figure 52) in the “

sTop

position, remove the key and store in a safe place.

Figure 52. Ignition Switch (Stop Position)

5. Remove all loads from the generator.
6. Inspect entire generator for any damage or loosening of

components that may have occurred during operation.

emergenCY shuTDoWn proCeDure

1. Turn ignition switch key to the

sTop position.

2. To shut-down the engine in the event of an emergency,

switch the

main, gFCi and loaD (Figure 50) circuit

breakers to

oFF position.

auTomaTiC shuT-DoWn sYsTem

This unit is equipped with safety devices to automatically

stop the engine in the event of low oil pressure, approximately

7 psi (49 kPa), or high water temperature, approximately

230° F (110° C). The alarm lamps on the Engine Control

Panel illuminate to signify the reason for the shutdown.

START/IDLE

NOTICE

Before inspecting, turn the ignition switch to the

sTop

position, place all circuit breakers in the

oFF position

and allow sufficient time for adequate cooling. When

ready to restart, complete all steps in the Generator

Startup Procedure section of this manual.

10. Place the

main, gFCi, and aux. circuit breakers in the

on position (Figure 48).

Figure 48. Main, Aux. and GFCI

Circuit Breakers (ON)

11. Observe the generator’s ammeter (Figure 49) and

verify it reads the anticipated amount of current with

respect to the load. The ammeter will only display a

current reading if a load is in use.

Figure 49. Ammeter (Load)

12. The generator will run until manually stopped or an

abnormal condition occurs.

normal shuTDoWn proCeDure

To shutdown the generator, use the following procedure:
1. Place both the

main, gFCi and loaD circuit breakers

as shown in Figure 50 to the

oFF position..

Figure 50. Main, GFCI and Load

Circuit Breakers Off

Warning

never stop the engine suddenly except in an

emergency.

This manual is related to the following products: