TROUBLESHOOTING

GENERAL TROUBLESHOOTING

SYMPTOM

POSSIBLE CAUSE

ACTION

1. Glass Soots

A. Flame impingement on logs

A. Install log set per the instructions

Inspect the injector and air intake area. Make sure this area does

not have any blockage from debris and clean.

Check gas supply.

2. Flame burn

blue and lifts

off burner

(ghosting)

A. Insufficient oxygen being supplied

A. Ensure that the vent cap is installed properly and free of debris.

Ensure that the vent system joints are tight and have no leaks.

Ensure that no debris has been blocking the inner air intake at the

bottom back of the combustion chamber. Ensure that the glass is

properly secure and latch.

GLASS REPLACEMENT

AND

BLOWER

• Never operate fireplace if glass is broken.
• Replace any glass that is chipped, cracked, or broken. Replacement glass assemblies MUST be supplied by fireplace

manufacturer — No substitute materials may be use.

Always use gloves when handling
broken glass.

CAUTION

Make sure the glass panel edges
do not touch any metal parts during
thermal expansion.

W

ARNING

OPTIONAL BLOWER ACCESSORY - BLOT

WIRING DIAGRAM FOR BLOWER