COMMON MATERIALS AND FACTORS

MATERIAL

K*

R

MINIMUM

THICKNESS

EH2416

Common Brick

0.916

5.0

2.18 1.0 in.**

0.10 5.46 in.**

(Majestic Products
Company)

R Value is for

¹⁄₂

inch.

* Units of K = BTU/SQ FT/HR/ßF/IN
** Thickness of Listed Material

FP533ADD

Fig. 23 Hearth extension material factors.

The top of insulation must be covered with a non-
combustible decorative covering or a piece of .018”
minimum sheet metal, to protect hearth extension
material. (Fig. 25)

Secure the hearth extension to the floor to prevent
shifting, using trim molding or other similar means at
three (3) outer edges. Seal crack between the fireplace
hearth and hearth extension with a noncombustible
material. (Figs. 24 and 25)

WARNING: Hearth extension must be installed in
accordance with Figure 24. Top of hearth extension
must be level with bottom of fireplace.

Alternate noncombustible materials may be used
providing the (total) thermal resistance (Rt value) of the
alternate material employed is greater than or equal to
R = 1.09 Thermal resistance (R) or thermal conductiv-
ity (K), may be obtained from manufacturer of the
material. Factors are related by the formula K = 1/R.
(Fig. 23)

T = given thickness
R = thermal resistance for a given thickness (T)
K = thermal conductivity

Noncombustible material with a lower R value may be
used, provided thickness of material is sufficiently
greater to maintain an equivalent (total) thermal resis-
tance (Rt).

Example of Determining Hearth Extension
Equivalents

To determine the thickness required for any new
material:

Example for Common Brick

T (new) = 5.0/0.458 x 0.50 in. = 5.46 in. (new required
thickness).

Wall Covering

2 x 4 Header - Do not
notch at standoffs

Noncombustible
Decorative
Facing

Seal all cracks
between fireplace
surround (steel) and
wall materials with
noncombustible
material.