Vermont Castings EWF36A

20005167

If the area above the ceiling is not an attic, position the
firestop spacer with the flange on the ceiling side and
the angled portion extending up into the hole.

If the area above the ceiling is an attic, position the
firestop spacer with the flange on the top of the framed
hole and the angled portion extending down into the
hole.

Firestop spacers are not available for, nor are they
required on vertical walls.

DO NOT put any sealant around the area where the
outer pipe slides through the firestop spacer. If you
seal this area, it may cause a fire hazard.

Nails (4)

Attic Installation

Joist

Firestop Spacer

Joist

Firestop Spacer

Nails (4)

Ceiling Installation

FP593

Fig. 17 Firestop spacer installations.

Canadian Requirements

for Insulation Shield

In Canada, an attic insulation shield is required to
prevent attic insulaiton from contacxting the chimney
section. Framing dimensions fr the chimney hole should
measure 17

¹⁄₂

” x 17

¹⁄₂

” (445mm x 445mm). An attic

shield MUST be installed on top of attic joists (above
the floor level). (Fig. 18)

Continue Installing Pipe to Complete Run

Continue attaching pipe sections to complete system to
next level always being careful that the pipe is firmly
snapped locked in place before proceeding to next pipe
section.

Chimney Supports

If chimney supports are required, they are installed the
same as elbows. Nail chimney support straps to
adjacent structural framing, as shown on Figure 16.
Bend straps as necessary and make sure they are
secure so they will support the weight of the chimney. A
chimney support is 2

¹⁄₂

" (64mm) long when installed.

Consider this dimension when determining how many
straight chimney sections are needed.

NOTE: Chimney supports are generally used in long
runs in a chase installation.

Additional Ceilings

If you encounter additional ceilings, repeat same steps
required for first ceiling installation. See firestop
illustration in Figure 17.

Penetrating the Roof

Run pipe to roofline. Since chimney system must be
vented to the out-of-doors, you must use an approved
Vermont Castings, Majestic Products termination.

If a chase is used, refer to the installation manual
provided with the termination cap.

Locate Chimney Centerpoint on Roof

Use same procedure detailed in locating center point of
the flue system.

Drive a nail up through roof at the center point. This will
determine center point on outside of the roof.

Cut and Frame Roof Hole

Size of roof hole varies with the type of chimney termi-
nation installed. Refer to installation instructions
provided with Vermont Castings, Majestic Products
chimney termination to find correct size of roof hole.

Attic Insulation
Shield

Nails
(4 Required)

Attic Joist

Ceiling

Base
Flanges

FP263

Fig. 18 Attic shield installation (Canadian requirement).