(1) LEV opening correction by suction super heat (COOL, DRY)
(Suction super heat) = (Minimum gas pipe temperature) - (Evaporation temperature)
When COOL and DRY , correct the LEV openings corrected from the table below
(2) Separate correction (COOL,DRY)
(When number of operation unit is 2 units or more)
(a) Correction by the separate super heat
Correct the LEV separately by temperature difference between each gas pipe temperature thermistor and evaporator
temperature thermistor.
1
Calculate each super heat of the unit from the expression below;
(Super heat) = (Gas pipe temperature thermistor) - (Evaporation temperature thermistor)
2
Select a minimum super heat from among them.
3
Correct an each LEV is corrected opening is corrected by difference between each super heat and minimum super
heat.
1
Suction super heat
(MIN gas pipe temperature thermistor - Evaporation temperature thermistor)
2
Each correction
w
1
• (Each gas pipe temperature thermistor - Evaporation temperature thermistor)
• (Main pipe temperature thermistor - sub pipe temperature thermistor)
w
1 Perform this, when number of operation units is 2units or more
w
2 When the correction opening of suction super heat is 0, correct the LEV opening by dischaege temperature.
3
Discharge temperature
COOL
DRY
HEAT
•
•
-
•
w
2
•
w
2
•