REFRIGERANT SYSTEM DIAGRAM
9
Unit:mm
●
Refrigerant pipe diameter is different according to indoor unit to be connected. When using extension pipes,refer to the
tables below.
●
When diameter of refrigerant pipe is different from that of outdoor unit union, use optional Different-diameter pipe.
For further information on Different-diameter pipe,see page BACK COVER.
Indoor unit
Extension pipe diameter
class
Pipe diameter
Liquid
6.35(1/4)
Liquid
6.35(1/4)
07/09
Gas
9.52(3/8)
Gas
9.52(3/8)
Liquid
6.35(1/4)
Liquid
6.35(1/4)
12(13)
Gas
12.7(1/2)
Gas
12.7(1/2)
Liquid
6.35(1/4)
Liquid
6.35(1/4)
18
Gas
15.88(5/8)
Gas
15.88(5/8)
Outdoor unit union diameter
For
Liquid
6.35(1/4)
Indoor unit A
Gas
12.7(1/2)
Liquid
6.35(1/4)
Indoor unit B
Gas
12.7(1/2)
Liquid
6.35(1/4)
Indoor unit C
Gas
9.52(3/8)
Liquid
6.35(1/4)
Indoor unit D
Gas
9.52(3/8)
Unit : mm (inch)
Piping length each indoor unit (a, b, c, d)
25m
Total piping length (a+b+c+d)
60m
Height difference between units (H)
10m
Bending point for each unit
25
Total bending point
60
❋
It does not matter which unit is higher.
a
b
c
d
Outdoor
unit
Indoor
units
H
H
H
Indoor unit
D
Ball valve with
service port
Ball valve with
service port
Distributor
Strainer
Strainer
LEV
Oil
separator
Compressor
High pressure
switch 1
Accumulator
Capillary tube
Reversing valve
Discharge
temperature
thermistor
Evaporation
temperature
thermistor
(RT67)
Defrost
thermistor
Strainer
Distributor
Outdoor
heat
exchanger
High pressure
switch 2
Unit D gas pipe temperature thermistor
[
9.52
Indoor unit
C
Unit C gas pipe temperature thermistor
[
9.52
[
6
Indoor unit
B
Unit B gas pipe temperature
thermistor
[
12
Indoor unit
A
Indoor unit
A
Strainer
LEV
[
6
Indoor unit
B
Strainer
LEV
[
6
Indoor unit
C
Strainer
LEV
[
6
Indoor unit
D
Unit A gas pipe
temperature thermistor
[
12
[
16
[
16
[
9.52
[
16
Capillary tube
[
2.5
✕[
0.6
✕
750
[
2.5
✕
[
0.6
✕
1000
Capillary tube
[
4.0
✕[
2.4
✕
400
Capillary tube
Capillary tube
Capillary tube
Capillary tube
[
3.0
✕[
2.0
✕
200
[
3.0
✕[
2.0
✕
200
[
3.0
✕[
2.0
✕
200
[
3.0
✕[
2.0
✕
200
Refrigerant flow in cooling
Refrigerant flow in heating
Reversing valve coil
heating ON
cooling OFF
MXZ-32SV -
MXZ-32SV -
E2
E1