Vent installation – Monessen Hearth Direct Vent Gas Fireplace BDV500 User Manual

Page 23

background image

54D0700

23

40' Maximum Height

8' Minimum Height

10'

Maximum

Support Straps

Every 3'

40' Maximum Height

8' Minimum Height

10'

Maximum

Support Straps

Every 3'

Support

Straps

Every

5'Vertical

VERTICAL (THROUGH-THE-ROOF) APPLICATIONS

This Gas Fireplace has been approved for,
• Vertical installations up to 40' (12m) in height. Up to a 10' (3m) horizontal vent run can be installed within the vent system

using a maximum of two 90° elbows. See Figure 28.

Figure 28 - Support Straps for Horizontal Runs

VENT INSTALLATION

Figure 29 - Maximum Elbow Usage

• Up to two 45° elbows may be used within the

horizontal run. For each 45° elbow used on the
horizontal plane, the maximum horizontal length
must be reduced by 18" (450mm).

Example: Maximum horizontal length

No elbows = 10’ (3m)

1x45° elbows = 8.5’ (2.6m)

2x45° elbows = 7’ (2.1m)

• A minimum of an 8' (2.5m) vertical rise is

required.

• Two sets of 45°elbows offsets may be used within

the vertical sections. From 0 to a maximum of 8'
(2.5 m) of vent pipe can be used between elbows.
See Figure 29.

• The maximum angular variation allowed in the

system is 270°. See Figure 29.

1

2

3

4

1

2

3

4

Example:

Elbow 1 = 90°

Elbow 2 = 45°

Elbow 3 = 45°

Elbow 4 = 90°

Total Angular Variation = 270°

NOTE: Horizontal sections of this vent system require a
minimum of 3" clearances to combustibles at the top of
the fl ue and 1" clearance at the sides and bottom until the
fl ue penetrates the outside wall. A minimum 1" clearance all
around the fl ue is acceptable at this point of penetration.

Vertical sections of this vent system require a minimum of
1" clearance to combustibles on all sides of the pipe.