3.3.2.2 Set Day of Week

T i m e : 2 2 : 5 5

D a y : 2 T u e s d a y

Figure 3-19 Set Day of the week

This display example shows that Tuesday is the current day of the week. The underline character indicates that
the day can be changed by entering the corresponding digit:

1

Monday

2

Tuesday

3

Wednesday

4

Thursday

5

Friday

6

Saturday

7

Sunday

3.3.2.3 Load Default Configuration

1 L o a d D e f a u l t

C o n f i g u r a t i o n

Figure 3-20 Load Default Configuration

When the one (1) digit is pressed, the panel will prompt for the password, even if it has been entered previously.
If the password is entered correctly, the panel will overwrite the existing configuration with the default
configuration. This operation is intended to restore the panel to a known basic condition if it is removed from
one installation and installed in another.

The default configuration is:

?

Password

1234

?

Sensors

Undefined

?

Alarm levels

CO = 200 ppm, HS = 5.0ppm, EX = 4,000 ppm

?

Alarm signals

Buzzer = Intermittent, Horn = Intermittent, Strobe = Continuous

?

Warning signals

Buzzer = Double Tap, Horn = Off, Strobe = Off

?

Trouble signals

Buzzer = Triple Tap, Horn = Off, Strobe = Off

?

Warning Levels

CO = 200 ppm, HS = 5.0 ppm, EX = 4,000 ppm

?

Sensor Range

CO = 200ppm, HS = 6.0 ppm, EX = 10,000 ppm

?

Relay 1

Normally off, 1 minute turn on delay, 1 minute minimum on time

?

Relay 2

Normally off, 1 minute turn on delay, 1 minute minimum on time

?

Relay 3

Normally off, 1 minute turn on delay, 1 minute minimum on time

?

Horn

Normally off, 1 minute turn on delay, 0 (zero) minimum on time

?

Strobe

Normally off, 1 minute turn on delay, 0 (zero) minimum on time

?

Zone1

Controls nothing, no sensors assigned, Voting mode, Quorum = 1

?

Zone2

Controls nothing, no sensors assigned, Voting mode, Quorum = 1

?

Zone3

Controls nothing, no sensors assigned, Voting mode, Quorum = 1

?

Rising Trip Levels CO = 100 ppm, HS = 2.5ppm, EX = 2,000 ppm

?

Falling Trip Levels CO = 50 ppm, HS = 1.2 ppm, EX = 1,000 ppm