PAGE 54 — DCA-180SSJU — OPERATION AND PARTS MANUAL — REV. #3 (02/01/10)

When the generator is set in the
AUTO mode, the generator will

in the event of

comercial power falling below a
prescribed level by means of a
contact closure that is generated
automatically by a transfer switch.

NOTE

Starting (Auto Mode)

Before connecting this generator to any
building’s electrical system, a

must install an

. Serious damage to the

building’s electrical system may occur
without this transfer switch.

DANGER - ELECTRICAL SYSTEM HAZARDS

When connecting the generator to a isolation (transfer)
switch, ALWAYS have power applied to the generator's
internal battery charger. This will ensure that the engine
will not fail due to a dead battery.

CAUTION - BACKUP GENERATOR USE

Figure 54. Main, Aux. and GFCI

Circuit Breakers (ON)

18. Place the

,

, and

. circuit breakers in the

ON position (Figure 54).

19. Observe the generator's ammeter

(Figure 55) and verify it reads the
anticipated amount of current with
respect to the load. The ammeter
will only display a current reading if
a load is in use.

Figure 55.

Ammeter (Load)

20. The generator will run until manually stopped or an

abnormal condition occurs.

GENERATOR START-UP PROCEDURE (MANUAL)

Figure 49. Voltage Adjust Control Knob

Figure 50.

Ammeter (No

Load)

14. The ammeter (Figure 50) will

indicate

with no load

applied. When a load is applied, the
ammeter will indicate the amount of
current that the load is drawing from
the generator.

Figure 53. Engine

Tachometer

Gauge

17. The

(Figure

53) will indicate the speed of the
engine when the generator is
operating. Under normal operating
conditions this speed is
approximately 1800 RPM’s.

16. The

(Figure 52) will indicate the
coolant temperature. Under
normal operating conditions the
coolant temperature should be
between 180~230°F (82~110 °C)

.

Figure 52. Coolant

Temperature Gauge

15. The engine oil pressure gauge

(Figure 51) will indicate the oil
pressure

of the engine. Under

normal operating conditions the oil
pressure is approximately 35 to 65
psi. (241~448 kPa). When starting
the generator

Figure 51. Oil

Pressure Gauge