Output terminal panel familiarization – Multiquip 60Hz Generator DCA180SSJU User Manual
Page 41

DCA-180SSJU — OPERATION AND PARTS MANUAL — REV. #3 (02/01/10) — PAGE 41
1
120 VAC GFCI Receptacles
There are two 120 VAC, 20 amp GFCI (Duplex Nema 5-
20R) recepacles provided on the output terminal panel.
These receptacles can be accessed in any
position. Each receptacle is protected by a 20 amp
circuit breaker. These breakers are located directly above
the GFCI receptacles. Remember the load output (current)
of both GFCI receptacles is dependent on the load
requirements of the U, V, and W output terminal lugs.
Pressing the
button resets the GFCI receptacle after
being tripped. Pressing the
(See Figure 10) in
the center of the receptacle will check the GFCI function.
Both receptacles should be tested at least once a month.
Figure 10. G.F.C.I. Receptacle
Each auxilliary receptacle is protected by a 50 amp circuit
breaker. These breakers are located directly above the GFCI
receptacles. Remember the load output (current) on all three
receptacles is dependent on the load requirements of the
.
Turn the
(Figure 12) on
the control panel to obtain the desired voltage. Turning the
knob clockwise will
the voltage, turning the knob
counter-clockwise will
the voltage.
Figure 11. 240/139V Twist-Lock
Auxiliary Receptacles
OUTPUT TERMINAL PANEL FAMILIARIZATION
Twist Lock Dual Voltage 120/240 VAC Receptacles
There are three 240/139V, 50 amp auxilliary twist-lock
(CS-6369) recepacles (Figure 11) provided on the output
terminal panel.These receptacles can
be accessed
when the voltage change-over board is configured for
Figure 12. Voltage Regulator Control Knob
Figure 13. Plastic Face Plate (Output Terminal
Lugs)
Removing the Plastic Face Plate (Hard Wire Hookup
Panel)
The
are protected by a plastic face
plate cover (Figure 13). Un-screw the securing bolts and lift
the plastic terminal cover to gain access to the terminal
enclosure.
After the load wires have been securely attached to the
terminal lugs, reinstall the plastic face plate.