beautypg.com

Generator outputs/ gauge reading – Multiquip 60Hz Generator DCA180SSJU User Manual

Page 45

background image

DCA-180SSJU — OPERATION AND PARTS MANUAL — REV. #3 (02/01/10) — PAGE 45

1

How to Read the AC Ammeter and AC Voltage Gauges.
The AC ammeter and AC voltmeter gauges are controlled
by the AC ammeter and AC voltmeter change-over switches.

Both of these switches are located on the control panel and
DO NOT effect the generator output. They are provided to
help observe the phase to phase voltage and the current
flowing to the load at the UVWO output terminals lugs.

Observe that the voltage change-over board (Figure 17) has
been configured for

3Ø,

240V operation.

Figure 18. AC

Voltmeter

Change-Over Switch

Figure 19. AC Voltmeter

Gauge

(Volt reading on W-U Lug)

Figure 21. AC Ammeter

(Amp reading on U lug)

Figure 20. AC

Ammeter

Change-Over Switch

The

gauge will only

show a reading when the

are

connected to a load and in use.

NOTE

GENERATOR OUTPUTS/ GAUGE READING

Figure 17. Change-Over Board

(3Ø 240V Configuration)

AC Voltmeter Gauge Reading

Place the

(Figure 18)

in the W-U position and observe the phase to phase voltage
reading between the W and U terminals as indicated on the

(Figure 19).

AC Ammeter Gauge Reading

Place the

(Figure 20)

to the U position and observe the current reading (load drain)
on the U terminal as indicated on the

(Figure 21). This process can be repeated for terminals V
and W.

This manual is related to the following products: