OUTPUT TERMINAL PANEL CONNECTIONS
Figure 22. Voltage Change-Over Board
240V
Configuration
UVWO Terminal Output Voltages
Various output voltages can be obtained using the UVWO
output terminal lugs. The voltages at the terminals are de-
pendent on the placement of the jumpers plates (6) on the
and the adjustment of the
.
Remember the voltage change-over board determines the
of the output voltage and can be configured in two
different positions that provide 6 different output voltages at
the UVWO output terminals. The generator is shipped from
the factory in the 240V configuration. The voltage regulator
(VR) allows the user to increase or decrease the selected
voltage.
3Ø-240V UVWO Terminal Output Voltages
1. Jumper the voltage change-over board for 240V
operation as shown in Figure 22.
Figure 23. UVWO Terminal Lugs
3Ø-240V Connections
2. Connect the load wires to the UVWO terminals as shown
in Figure 23.
3. Turn the voltage regulator knob (Figure 24) clockwise
to increase voltage output, turn counterclockwise to
decrease voltage output. Use voltage regulator
adjustment knob whenever fine tuning of the output
voltage is required
Figure 24. Voltage Regulator Knob
1Ø-240V UVWO Terminal Output Voltages
1. Make sure the voltage change-over board is jumpered
for 240V operation as shown in Figure 22.
2. Connect the load wires to the UVWO terminals as shown
in Figure 25.
Figure 25. UVWO Terminal Lugs
1Ø-240V Connections
Figure 26. UVWO Terminal Lugs
1Ø-120V Connections
1Ø-120V UVWO Terminal Output Voltages
1. Make sure the voltage change-over board is jumpered
for 240V operation as shown in Figure 22.
2. Connect the load wires to the UVWO terminals as shown
in Figure 26.