Water Supply and Drain Requirements
WATER SUPPLY
Local water conditions may require treatment of the
water to inhibit scale formation, filter sediment, and
remove chlorine odor and taste.
AIR GAP
An air gap is incorporated into the design of the ice
machine. Maximum water level is the top of the water
trough, which allows a minimum 1 inch air gap.
WATER INLET LINES
Follow these guidelines to install water inlet lines:
•
Do not connect the ice machine to a hot water
supply. Be sure all hot water restrictors installed for
other equipment are working. (Check valves on sink
faucets, dishwashers, etc.)
•
If water pressure exceeds the maximum
recommended pressure, obtain a water pressure
regulator from your Manitowoc distributor.
•
Install a water shut-off valve for both the ice making
and condenser water lines.
•
Insulate water inlet lines to prevent condensation.
DRAIN CONNECTIONS
Follow these guidelines when installing drain lines to
prevent drain water from flowing back into the ice
machine and storage bin:
•
Drain lines must have a 1.5 inch drop per 5 feet of
run (2.5 cm per meter), and must not create traps.
•
The floor drain must be large enough to
accommodate drainage from all drains.
•
Run separate bin and ice machine drain lines.
Insulate them to prevent condensation.
•
Vent the bin and ice machine drain to the
atmosphere. Do not vent the condenser drain on
water-cooled models.
Cooling Tower Applications
(Water-Cooled Models)
A water cooling tower installation does not require
modification of the ice machine. The water regulator
valve for the condenser continues to control the
refrigeration discharge pressure.
It is necessary to know the amount of heat rejection, and
the pressure drop through the condenser and water
valves (inlet and outlet) when using a cooling tower on
an ice machine.
•
Water entering the condenser must not exceed 90°F
(32.2°C).
•
Water flow through the condenser must not exceed 5
gallons (19 liters) per minute.
•
Allow for a pressure drop of 7 psi (48 kPA) between
the condenser water inlet and the outlet of the ice
machine.
•
Water exiting the condenser must not exceed 110°F
(43.3°C).
Important
If you are installing a Manitowoc Arctic Pure™ water
filter system, refer to the Installation Instructions
supplied with the filter system for ice making water
inlet connections.
! Caution
Do not apply heat to water valve inlet fitting. This will
damage plastic valve body.