Electrical Service

GENERAL

VOLTAGE

The maximum allowable voltage variation is ±10% of the
rated voltage at ice machine start-up (when the electrical
load is highest).

FUSE/CIRCUIT BREAKER

A separate fuse/circuit breaker must be provided for
each ice machine. Circuit breakers must be H.A.C.R.
rated (does not apply in Canada).

MINIMUM CIRCUIT AMPACITY

The minimum circuit ampacity is used to help select the
wire size of the electrical supply. (Minimum circuit
ampacity is not the ice machine’s running amp load.)

The wire size (or gauge) is also dependent upon
location, materials used, length of run, etc., so it must be
determined by a qualified electrician.

ELECTRICAL REQUIREMENTS

Refer to Ice Machine Model/Serial Plate for voltage/
amperage specifications.

S Series Marine Ice Machines

!

Warning

All wiring must conform to local, state and national
codes.

!

Warning

The ice machine must be grounded in accordance
with national and local electrical codes.

Important

Observe correct polarity of incoming line voltage.

Ice Machine

Voltage Phase

Cycle

Water Cooled

Maximum Fuse/Circuit

Breaker

Minimum Circuit Amps

S1000M

208-230/1/60

20

12.6

208-230/3/60

15

8.9

230/1/50

20

11.2